GFK-1868Q

реклама
Proficy*
Machine Edition
GETTING STARTED
Version 7.50
2012
GFK-1868Q
2
Getting Started first draft
All rights reserved. No part of this publication may be reproduced in any form or by any
electronic or mechanical means, including photocopying and recording, without permission in
writing from GE Intelligent Platforms, Inc.
Disclaimer of Warranties and Liability
The information contained in this manual is believed to be accurate and reliable. However, GE
Intelligent Platforms, Inc. assumes no responsibilities for any errors, omissions or
inaccuracies whatsoever. Without limiting the foregoing, GE Intelligent Platforms, Inc.
disclaims any and all warranties, expressed or implied, including the warranty of
merchantability and fitness for a particular purpose, with respect to the information contained
in this manual and the equipment or software described herein. The entire risk as to the
quality and performance of such information, equipment and software, is upon the buyer or
user. GE Intelligent Platforms, Inc. shall not be liable for any damages, including special or
consequential damages, arising out of the use of such information, equipment and software,
even if GE Intelligent Platforms, Inc. has been advised in advance of the possibility of such
damages. The use of the information contained in the manual and the software described
herein is subject to GE Intelligent Platforms, Inc. standard license agreement, which must be
executed by the buyer or user before the use of such information, equipment or software.
Notice
GE Intelligent Platforms, Inc. reserves the right to make improvements to the products
described in this publication at any time and without notice.
© 2012 GE Intelligent Platforms, Inc. All rights reserved. * Trademark of GE Intelligent
Platforms, Inc. Any other trademarks referenced herein are used solely for purposes of
identifying compatibility with the products of GE Intelligent Platforms, Inc.
We want to hear from you. If you have any comments, questions, or suggestions about our
documentation, send them to the following email address:
doc.ip@ge.com
4
Getting Started first draft
Contents
1 Contents
i
2 Welcome
1
System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Product Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Hardware Key Authorization
...............................5
Software Key Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Contact GE INTELLIGENT PLATFORMS . . . . . . . . . . . . . . . . . . . . . . . 10
General Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Americas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Europe, the Middle East, and Africa (EMEA) . . . . . . . . . . . . . . . . . . 10
Asia Pacific . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3 Proficy* Machine Edition*
13
Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Machine Edition Environment
................................
Getting to Know Machine Edition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Right-click, right-click, right-click . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing the Right Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using docking markers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Projects and the Navigator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Properties and the Inspector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Watch Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smart Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The Toolchest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The Feedback Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Managing Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Machine Edition Projects
....................................
Sharing Projects between Machine Edition Workstations . . . . . . . . .
Running a Sample Project (View/Logic Developer - PC) . . . . . . . . .
Developing a Machine Edition Project . . . . . . . . . . . . . . . . . . . . . . .
Validating and Downloading a Project . . . . . . . . . . . . . . . . . . . . . . .
Testing a View Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GFK-1868Q
14
16
17
17
17
19
19
20
22
23
24
25
26
27
29
29
30
32
35
37
Proficy* Machine Edition* 7.50 i
Contents
4 Logic Developer - PC
39
SFC Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sequential Function Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the SFC editor - Offline . . . . . . . . . . . . . . . . . . . . . . . .
Working with the SFC editor - Online . . . . . . . . . . . . . . . . . . . . . . . .
Ladder Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ladder Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the ladder editor - Offline . . . . . . . . . . . . . . . . . . . . . . .
Working with the ladder editor - Online . . . . . . . . . . . . . . . . . . . . . . .
Instruction List Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the IL editor - Offline . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the IL editor - Online . . . . . . . . . . . . . . . . . . . . . . . . . .
Structured Text Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Structured Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the ST editor - Offline . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the ST editor - Online . . . . . . . . . . . . . . . . . . . . . . . . .
Function Block Diagram Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the FBD editor - Offline . . . . . . . . . . . . . . . . . . . . . . . .
Working with the FBD editor - Online . . . . . . . . . . . . . . . . . . . . . . . .
Logic Developer - PC Web Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control I/O Drivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Drivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control I/O Tool
........................................
Working with Control I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warm Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with Warm Standby
..............................
Hot Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with Hot Standby
................................
OPC Servers, Warm Standby, and Hot Standby . . . . . . . . . . . . . . .
5 View*
41
41
42
44
45
45
46
47
49
49
50
51
52
52
53
54
55
55
56
58
59
62
62
63
64
65
66
67
68
68
68
69
71
Panel Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Working with the Panel Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
ii
Proficy* Machine Edition* 7.50
GFK-1868Q
Contents
Message Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Script Editor
..............................................
Scripts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scripting Languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VBScript Syntax . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Active Scripting Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the Script Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grid Editors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm Display Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Logging data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC Access I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPC Client . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Machine Edition OPC Servers . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
View Web Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Languages folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Working with the Languages editor . . . . . . . . . . . . . . . . . . . . . . . . . .
View Runtime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Networking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QuickPanel Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External Keypad Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scripts on QuickPanel Targets . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QPScript Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Motion Developer*
99
About Motion Developer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supported motion control devices . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion targets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion Scripts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion wizards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Wizards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GFK-1868Q
GFK-1868Q
74
75
75
76
78
78
78
79
80
80
81
82
83
83
85
86
86
87
90
91
93
93
95
95
96
96
100
100
101
101
102
103
104
105
106
108
Proficy* Machine Edition* 7.50
iii
Contents
Application Builder flowchart editor . . . . . . . . . . . . . . . . . . . . . . . . . 108
Motion Calculator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
CAM Profile Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Index
iv
Proficy* Machine Edition* 7.50
115
GFK-1868Q
1
Welcome
Congratulations on your purchase of a Proficy* Machine Edition* 7.50 product.
This package provides all the tools necessary to create powerful control and HMI
(human machine interface) applications for a variety of run-time targets; a truly
scalable solution. Machine Edition supports the following products and features:
■
A fully-integrated environment. Every tool and editor works with the others.
■
Logic Developer - PC*, scalable, computer based control software with a
complete set of IEC standard editors (available with QuickPanel Control
products).
■
Logic Developer - PLC*, a software tool for programming the full line of GE IP
Controllers. (See GFK-1918 Getting Started Logic Developer - PLC.)
■
View*, for creating HMIs for Windows 7, Windows XP, QuickPanel
View/Control, and QuickPanel units.
■
Motion Developer*, for developing Whedco motion control applications.
■
Web Access features that access real-time HMI data any time, from anywhere.
View
Logic
Developer
PC
Logic
Developer
PLC
Motion
Developer
Machine Edition Environment
(Development Tools)
Build & Download
Runtime Files
QuickPanel Control
Build & Download
Runtime Files
QuickPanel QuickPanel
View
Build & Download
Runtime Files
GE IP Controllers
Build & Download
Runtime Files
Motion Controllers
Remote I/O
I/O Modules
Web Access
GFK-1868Q
Motors/Drives
Internet/Intranet
Proficy* Machine Edition* 7.50
1
1
Welcome
System Requirements
SYSTEM REQUIREMENTS
To use Machine Edition and its tools, you require the following:
Development Environmen t Operating System
Machine Edition product
Windows
7a
Windows
XP b
Logic Developer - PC
yes
yes
View
yes
yes
Logic Developer - PLC
yes e
yes
Logic Developer - State
yes
Motion Developer
yes
a. 32-bit or 64-bit variations of the following: Windows 7 Ultimate, Windows 7 Enterprise, or
Windows 7 Professional.
Want to know more? In the Help Index, look up “Windows 7: Caveats”.
b. Supported: Windows XP Professional SP2 and SP3. You must be part of the PowerUsers
group or the Administrators group. Not supported: Windows XP Tablet PC Edition and
Windows XP Embedded.
c. Windows regional settings must be set to English
Processor speed and memory
■
Minimum: Intel Core Duo or AMD Athlon 64 X2 with 4 GB RAM
■
Recommended: 2.6 GHz Intel Core i series with 4 GB RAM
Other requirements
■
Internet Explorer version 8.0, 7.0, version 6.0 SP1 or later, or version 5.5 SP2
Q810847 or later.
Note: You must install Internet Explorer before installing Machine Edition.
■
TCP/IP Network protocol (if you use an Ethernet connection).
■
.NET Framework 4.0 Client Profile. If the Microsoft .NET Framework is not
yet installed, it is automatically included during the installation of Machine
Edition, and a reboot may be required to complete the installation.
■
2 GB hard disk space for all the Machine Edition products and sample
projects. Additional space is required for your projects and temporary files.
The Development Environment is supported on VMWare Player 2.0 or greater or
VMWare Workstation 6.0 or greater
Note: The APM Motion Programmer does not function if Machine Edition runs within VMWare.
2
Proficy* Machine Edition* 7.50
GFK-1868Q
Welcome
System Requirements
Windows P C Run time
■
If you install only the Runtime for Logic Developer - PC and View Developer,
the run-time executables are automatically updated from the development
machine when the project is downloaded.
■
32-bit or 64-bit variations of Windows 7 Ultimate, Windows 7 Enterprise, or
Windows 7 Professional; Windows XP Professional SP2 or SP3; or Windows
XP Embedded.
Notes
■
■
■
Windows regional settings must be set to English.
Windows XP Tablet PC Edition are not supported.
233 MHz Pentium-based workstation (1.6 GHz recommended)
Note: 300 MHz is required for Windows XP Professional.
■
200 MB free hard disk space.
■
128 MB RAM (1 GB recommended; minimum 256 MB on XP).
■
Minimum requirements for the range of variables defined in your projects:
Requirements
Variables
<500
500 - 10000
>10000
CPU
233 MHz
1 GHz
2 GHz
Disk Space
200 MB
200 MB
200 MB
RAM
128 MB
512 MB
1 GB
QuickPanel View/Control Runt ime
GFK-1868Q
■
For HMI and Logic components: QuickPanel Control.
■
For HMI only: QuickPanel View.
Proficy* Machine Edition* 7.50
3
1
Welcome
Installation
INSTALLATION
For last-minute information, release notes, and supported hardware lists for
Machine Edition products, see the Important Product Information (IPI) document
on the DVD. There are several ways to view this document:
■
■
■
■
When installing Machine Edition, select Important Product Information on
the initial Launcher screen.
On the Machine Edition Help menu, choose Important Product Information.
When running Machine Edition, click the InfoView tab in the Navigator, then
double-click the Important Product Information page under Getting Started in
the Table of Contents.
When running Machine Edition, click the Home button on the InfoViewer
toolbar, and click the What’s New link under Get Started on the left hand side.
If you have any problems installing Machine Edition, please contact Technical
Support (see page 9).
T o ins tal l the f u l l M ac hi ne Edi t io n d ev elopme nt environm ent f rom a D V D
1. Insert the Machine Edition DVD into your computer.
Windows automatically starts the setup program. If the setup program does not
automatically start, run Setup.exe in the root directory of the DVD.
2. Click Install to start the install process.
3. Follow the instructions that appear.
If a previous version of Machine Edition is installed on your workstation, you will
be prompted to uninstall Machine Edition during the upgrade process. You
should do so only when asked to by the installation process. Do not delete files
left behind during uninstallation; these will be used by the new version.
To ins tall only the View and Logic De veloper - PC Run-t i mes f rom a DV D
1. Insert the Machine Edition DVD into your computer.
Windows automatically starts the setup program. If the setup program does not
automatically start, run Setup.exe in the root directory of the DVD.
2. Click Install to start the install process.
3. Follow the instructions that appear until you reach the Proficy Machine Edition
Setup page.
4. On that page, expand the View node. Under that node, select Run-time and
deselect everything else. Expand the Logic Developer - PC node. Here too,
select Run-time and deselect the rest. At the bottom of the page, click Next.
5. Follow the instructions that appear.
4
Proficy* Machine Edition* 7.50
GFK-1868Q
Welcome
Product Authorization
PRODUCT AUTHORIZATION
A new installation of Proficy Machine Edition provides a 4-day trial license with
full access to Machine Edition features. This license overrides all other licensing
and cannot be removed. Any licensing added will be apparent on the fifth day.
View Runtime can be run for 2-hour demo periods at any time. Using View OPC
drivers with View Runtime on a PC requires a separate View license on the PC.
To continue using Machine Edition beyond the 4-day trial period, you must
authorize the software.
Two types of authorization are available: software key authorization and
hardware key authorization. On a single computer, it is not recommended to use
both types of authorization.
Hardware Key Authorization
A M4 or MAX USB hardware key contains authorization files that are read by the
Proficy Common License Viewer, which enables Proficy products, including one
or more Machine Edition products, to execute.
To see wha t product s and ta rget type s are a uthori z ed by a har dw are k ey
• On the Windows Start menu, point to Programs, then to Proficy Common, and
choose License Viewer.
To authoriz e Machine Edition product s with a har dw are k ey
1. Find out which version of the Proficy Licensing Software is installed on your
computer: On the operating system’s Start menu, point to Programs, then to
Proficy Common, and choose License Viewer. In the top right corner of the
License Viewer window that appears, click About. Take note of the version
number and click OK.
2. If this is the first time you install a Proficy product, access http://support.ge-
ip.com, and in the top right corner, click Register. In the Single Sign On page
that appears, enter your email address and click Submit. When you receive a
GE Intelligent Platforms Web Access Registration email, follow the instructions.
In the Single Sign On -- SSO Registration application window that appears, fill
out the information and click Submit.
3. Access http://support.ge-
ip.com/support/index?page=securitykey&id=ST15&lclicked=Licensing Key
Updates (login req). Enter your SSO User ID and Password. In the middle of the
GFK-1868Q
Proficy* Machine Edition* 7.50
5
1
Welcome
Product Authorization
page that appears, follow the Updating the Max/M4 or Pro/M1 key procedure,
keeping in mind the following:
■
Machine Edition does not support the insertion of a hardware key into a
parallel port, the insertion of hardware keys in multiple USB ports, or the
combination of a hardware key with a software key on the same computer.
■
If the web site refers to a more recent version than the one on your computer,
uninstall your current version, download the more recent version, and install
it.
■
The USB port is usually located on the front or back of your tower case, or in
the side of a laptop. We do not recommend using a USB port on your monitor.
■
If this is a new hardware key, double-click the license file <serialnumber>.plic
(supplied by your local distributor). In the wizard that appears, accept all the
defaults. The license file will be flashed onto your key.
■
The first time you plug the key into a USB port, you see a progress dialog box
that indicates that Windows has detected new hardware and is updating its
system settings. After the dialog box disappears, the settings stored in the
hardware key are active and you can use the products that it authorizes.
You must leave the key in the port while using the products. If you remove the
key from the port, authorization for those products is removed and replaced with
read-only access to your projects or a 2-hour demo mode for Runtime.
To move t he hardwa re- key authoriz at ion t o a nother comput er
• Remove the hardware key from the source computer and follow the previous
procedure on the destination computer.
After the authorization file <serialnumber>.plic has been flashed to the M4 or
MAX hardware key, it can be used on any computer on which the current version
of the Proficy Common License Viewer is installed.
Software Key Authorization
When authorizing Machine Edition products with a software key, you need to
contact us by telephone, fax, or e-mail. Authorization personnel are available on
the telephone between 6 a.m. and 6 p.m. MST.
Software key authorization is specific to a single computer or workstation. If you
want to work with Machine Edition on a different workstation, you must move the
authorization to that second workstation (see page 8).
6
Proficy* Machine Edition* 7.50
GFK-1868Q
Welcome
Product Authorization
To see wha t product s and ta rget type s are a uthori z ed by a sof twa re ke y
• On the operating system Start menu, point to Programs, then to Proficy (or GE
Fanuc or CIMPLICITY Machine Edition, depending on when Machine Edition
was first installed on the computer), then to Proficy Machine Edition, and then
choose Product Authorization.
To authori z e a copy of Ma chi ne E dit i on wit h a sof twar e key
1. Have your serial number(s) ready. The serial numbers can be found on the
Certificate of Authenticationt that came with your product.
2. Run the Product Authorization program from the Start menu | Programs | Proficy
| Proficy Machine Edition | Product Authorization.
3. In the Product Authorization dialog box that appears, click Add.
4. Select the means by which you are authorizing: Internet, Phone/Fax/E-mail or
Floppy Disk Transfer. Click Next.
If you choose the Internet option, follow the instructions on the web site.
If you choose the Phone/ Fax/ Email option, proceed to step 5.
If you choose the Floppy Disk Transfer option, ensure that you have an
authorization removable media to proceed.
5. Fill in the fields in the dialog box. Fields identified with an asterisk (*) must be
filled in.
If authorizing online click Submit Authorization once the form is completed.
If authorizing via phone/fax, click the Phone/Fax button once the form is
completed and call the number on the screen to receive a new key code(s).
If authorizing via e-mail, click the Send E-mail button once the form is complete.
■
Phone. Phone the number listed on the screen to receive a new key code(s).
■
Fax. Click Print FAX and fax the Product Authorization Request to us (our fax
number will be on the print out). We will then reply by fax with your new key
code(s).
■
Internet. On the Authorization web page, click Submit Authorization. We will
then reply by e-mail with your new key code(s).
■
E-mail. Click Authorize to e-mail us. We will then reply by e-mail with your
new key code(s).
Product Authorization is complete after you enter the new key code and it has
been accepted. Depending on the product you have purchased, you may need
to run the Product Authorization program a number of times.
GFK-1868Q
Proficy* Machine Edition* 7.50
7
1
Welcome
Product Authorization
To move t he sof twa re- key a uthoriz ation to a nother c ompute r
You can run a Machine Edition development product or Runtime only on the
computer on which the authorization process was completed. If you want to
develop your projects or execute Runtime on a different computer, you need to
complete the following steps to move the authorization from one computer to
another. (For a more detailed procedure with screen shots, access www.geip.com/support and look up Knowledge Base article KB5659.)
On the computer that the authorization will be moved to, do as follows:
1. Install Machine Edition.
2. Run the Product Authroization program as follows: on the operating system’s
Start menu, point to Programs, then to Proficy (or GE Fanuc or CIMPLICITY
Machine Edition, depending on when Machine Edition was first installed on the
computer), then to Proficy Machine Edition, and then choose Product
Authorization.
3. In the top right corner of the Product Authorization dialog box that appears, take
note of the Site Code.
This code is required to generate the license file on the source computer.
4. Leave the dialog box open.
On the source computer, do as follows:
1. Run the Product Authorization program. Select the authorized products you
want to move and click Move.
2. In the Before Moving message box that appears, read the note and click OK.
3. Enter the Site Code that you wrote down when you were on the destination
computer.
If the Site Code is entered incorrectly, the authorization will be lost and cannot
be recovered; you will need to contact technical support (see page 10).
4. Click Next.
5. In the Confirm dialog box that appears, verify that the site code is correct. If it is,
click OK.
6. Insert a blank formatted removable medium in the appropriate location.
7. In the refreshed Product Authorization dialog box, select the drive letter that
corresponds to the medium you inserted.
Do not select the C:\ drive; otherwise, your source license files will be
overwritten.
8. Click Next.
9. In the window that appears, confirm the accuracy of the Target Site Code. If it is
correct, click Finish.
8
Proficy* Machine Edition* 7.50
GFK-1868Q
Welcome
Product Authorization
The authorization code is moved to a file named authoriz.dat on the removable
medium you selected.
10. In the Authorization disk successfully created message box, read the message
and click OK.
On the destination computer, do as follows:
1. Insert the removable medium.
2. In the Product Authorization window that you left open earlier, click Add.
3. In the refreshed Product Authorization dialog box, select Floppy Disk Transfer
and click Next.
4. In the refreshed dialog box, to the right of the Please insert your Authorization
Disk field, click the button.
5. In the dialog box that appears, select the drive letter that corresponds to the
medium you inserted and navigate to the location of the authoriz.dat file. Click
Open.
6. In the Product Authorization dialog box, click Next.
7. In the refreshed dialog box, verify the product and contact information. If all is
correct, click Finish.
8. In the message box that indicates that the move was successful, click OK.
The authorization has now been moved to the new computer, as you can see in
the refreshed Product Authorization window.
9. Click Exit.
To change a s oft ware k ey to a ha rdware key or v ic e- vers a
• Contact your local distributor.
GFK-1868Q
Proficy* Machine Edition* 7.50
9
1
Welcome
Contact GE INTELLIGENT PLATFORMS
CONTACT GE INTELLIGENT
PLATFORMS
If you purchased this product through a GE Intelligent Platforms Authorized
Channel Partner, please contact the seller directly.
General Contact Information
Online Technical Support & GlobalCare: www.ge-ip.com/support
Comments about our manuals or online help: doc.ip@ge.com
Additional information: www.ge-ip.com
Solution Provider: solutionprovider.ip@ge.com
Authorization: authorization.ip@ge.com
Technical Support
If you have technical problems that cannot be resolved with the information in
this guide, please contact us by telephone or email, or on the web at www.geip.com/support.
Americas
Online Technical Support: www.ge-ip.com/support
Phone: 1-800-433-2682
International Americas Direct Dial: 1-434-978-5100
Technical Support Email: support.ip@ge.com
Customer Care Email: customercare.ip@ge.com
Inside Sales: insidesales.ip@ge.com
Primary language of support: English
Europe, the Middle East, and Africa (EMEA)
Online Technical Support: www.ge-ip.com/support
Phone: +1 800 433-2682 or +1 780-401-7717 if the 800 option is not available
in your country, or if dialing from a mobile telephone
Technical Support Email: support.emea.ip@ge.com
Customer Care Email: customercare.emea.ip@ge.com
Inside Sales: insidesales.emea.ip@ge.com
Primary languages of support: English, French, German, Italian, Czech,
Spanish
10
Proficy* Machine Edition* 7.50
GFK-1868Q
Welcome
Contact GE INTELLIGENT PLATFORMS
Asia Pacific
Online Technical Support: www.ge-ip.com/support
Phone: +86-400-820-8208
+86-21-3217-4826 (India, Indonesia, and Pakistan)
Technical Support Email: support.cn.ip@ge.com (China)
support.jp.ip@ge.com (Japan)
support.in.ip@ge.com (other Asias locales)
Customer Care Email: customercare.apo.ip@ge.com
customercare.cn.ip@ge.com (China)
GFK-1868Q
Proficy* Machine Edition* 7.50
11
1
12
Welcome
Contact GE INTELLIGENT PLATFORMS
Proficy* Machine Edition* 7.50
GFK-1868Q
2
Proficy* Machine Edition*
Proficy* Machine Edition* offers you a complete solution for the development of
automation applications under one roof. With Machine Edition’s integrated
development environment and tools, you will spend more time building
applications and less time learning the software.
Machine Edition products are fully integrated with the environment and with each
other:
■
■
■
■
They share the same project database. No more wasted time synchronizing
data points between applications!
They share the same set of tools, providing a consistent user interface
throughout the development process.
They feature full drag-and-drop capabilities between tools and editors.
They feature a true scalable solution. You can choose what type of machine
your projects are downloaded to and will run on.
The first part of this chapter provides an overview of the Machine Edition
environment. The second part provides some key Machine Edition concepts you
need to know before you begin. The third part shows how to open and explore
some of the sample projects included with a new Machine Edition installation.
When you have finished, you will have a solid foundation for building your own
automation projects.
■
GFK-1868Q
For more help getting started, in the
the Getting Started library.
InfoView tab of the Navigator, expand
Proficy* Machine Edition* 7.50
13
2
Prof icy* Machine Edition*
Quick Start
QUICK START
Machine Edition makes it easy to develop a project.
To st art Ma chi ne E dit i on
1. On the Windows toolbar, click
, point to All Programs, then Proficy, then
Proficy Machine Edition, and then click Proficy Machine Edition. (See also
page 30.)
When Machine Edition initializes for the first time following installation, the
Environment Themes dialog box appears.
You can change the default theme later by clicking the Window menu and
choosing Apply Theme.
2. Choose the environment theme you want to work in.
3. Click OK.
When you open a project, the appearance of your Machine Edition screen
matches the preview in the Environment Themes dialog box. As you work, you
can modify the environment – opening and closing windows, changing the
selected toolbars, and so on. Any changes are retained in your default
environment setup.
14
Proficy* Machine Edition* 7.50
GFK-1868Q
Prof icy* Machine Edition*
Quick Start
The Machine Edition dialog box appears.
Select this option to create a new, empty project.
Select this option to create a new project based
on a Machine Edition
project template.
Select this option to work
on an existing project
Select this option to
choose from those projects that have been
used recently.
Select this option to
choose from all existing
projects
Select this option if you
do not want to see this
dialog box again.
4. Select the appropriate option to open a project. The Open an existing project
option is selected by default.
Notes
■
■
If you select either Empty project or Machine Edition template, the New
Project dialog box appears, in which you can create a new project.
If you select Open an existing project, you can choose from Recent Projects
(the default) or All Projects. You may need to also specify the location of the
project: whether it is located on the local computer (My Computer), in a
shared folder (Shared Projects), or on Change Management Server (Server).
5. If you selected the Open an existing project option, select the project that you
want to open from the list.
Existing projects include samples and tutorials that you can use to familiarize
yourself with Machine Edition.
6. If desired, select the do not show this dialog box on startup option.
7. Click OK.
Your project opens in the Machine Edition environment that you specified in the
Environment Themes dialog box. For more information, see “Machine Edition
Projects” on page -29.
GFK-1868Q
Proficy* Machine Edition* 7.50
15
2
Prof icy* Machine Edition*
Machine Edition Environment
MACHINE EDITION ENVIRONMENT
All Machine Edition tools and editors appear in the Machine Edition window. The
run-time programs are separate Windows applications, so you can run a finished
application without starting Machine Edition.
The following illustration shows a possible layout of the tools and a couple of the
editors available to you. Most of the time, you will be using only a few of these at
once—you can open and close tools and editors as you need them. Many tools
are also available only when editing a project. We will look at some of the tools in
the following section; for more details on the others, see the online Help.
Navigator:
Organizes and
displays project
information in a
tree structure.
Toolchest:
Contains preconfigured
objects that you
can drag into
Machine Edition
projects.
Navigator tabs:
Conveniently
layers information about your
projects.
Inspector:
Displays the
properties of a
selected object.
InfoViewer:
An embedded
browser used
to display
reports and
comprehensive help.
Companion:
A dynamic help
window that provides information based on
what you are
doing.
Tabbed Editor window:
One of many windows where you create and
edit your application. Tabs at the top let you
switch between active Tabbed Editor windows with the click of a mouse.
16
Proficy* Machine Edition* 7.50
Common Machine Edition Tools
Data Watch:
Displays the current status of your
project’s variables.
Feedback
Zone: Displays output
information
generated by
Machine Edition components.
GFK-1868Q
Prof icy* Machine Edition*
Getting to Know Machine Edition
GETTING TO KNOW MACHINE
EDITION
The following are some key features of the Machine Edition environment.
Knowing them will make your first few hours with Machine Edition a breeze.
Right-click, right-click, right-click
No matter what object appears on your screen while using Machine Edition, you
can right-click it to perform operations on it. In fact, this is probably the most
common way you will get things done. Machine Edition tailors the menu of
commands depending on the current status of your project.
Getting Help
There are many ways to access the Machine Edition online help system.
■
■
■
■
■
Press F1 on any selected item for context-sensitive help.
Browse through the table of contents in the
InfoView tab of the Navigator.
Perform a full-text search of the help in a separate HTML Viewer window: on
the Help menu, choose Search.
Search for keywords using the index: on the Help menu, choose Index.
Use the
Companion to dynamically display a brief description about
whatever item you have selected.
You can also access additional help on the web. In Machine Edition on the Help
menu, point to Proficy on the Web, and then choose:
■
■
GFK-1868Q
Proficy Support
GE IP Home Page
Proficy* Machine Edition* 7.50
17
2
Prof icy* Machine Edition*
Getting to Know Machine Edition
Machine Edition provides two kinds of Help windows to display help information:
the Companion and the InfoViewer.
For detailed context-sensitive help, select
any item (in this case, a button on a graphical panel) and press F1.
To access the
online Help
index, on the
Help menu,
choose Index.
To access the
full-text search
viewer, on the
Help menu,
choose
Search.
Use the InfoViewer toolbar
to navigate the
HTML help.
The InfoViewer
window is a
browser that
displays the
comprehensive
HTML-based
online help.
The InfoView
Tab contains
the table of contents for the
online help.
Double-click a
page to view it.
Click this button
to open the InfoViewer with more
detailed information on the topic
in the Companion.
The Companion is a
dynamic help
window that
displays snippets of information on any
selected item.
Getting Help
Companion
The Companion window displays brief information about whatever item you are
working with, anywhere in Machine Edition. Whether you need the meaning of a
property, the purpose of a node in the Navigator, or an explanation of errors
generated during validation, the Companion is always there for you.
By default, the Companion is open while editing projects. If it has been turned
off, click
on the Tools toolbar to open it.
I nfoViewer
The InfoViewer window is an embedded Web browser that provides more
detailed and procedural help. It is launched whenever you access help topics
from the InfoView Tab, the help index, or by pressing F1 on a selected item.
Want to know more? In the Help Index, look up “Help” and choose “Finding information in
the Help”.
18
Proficy* Machine Edition* 7.50
GFK-1868Q
Prof icy* Machine Edition*
Getting to Know Machine Edition
Accessing the Right Tool
Often, Machine Edition Help will direct you to a specific tool window. If the tool
isn't visible, there are two ways to open it:
■
■
On the Tools menu, choose the tool name.
On the Tools toolbar, click the tool icon. To display the Tools toolbar, on the
Tools menu, choose Toolbars and select a menu item.
InfoViewer
Naviga-
Companion
Toolchest
Control I/O
Feedback
Data Watch
Inspector
Tools Toolbar
If you are not sure of the name of a tool within a toolbar, hover the mouse pointer
over the tool’s button to display its name in a tool tip.
Want to know more? In the Help Index, look up “Toolbars: an Overview”.
Using docking markers
If the Show Docking Markers option is enabled, you can use docking markers to
help dock a tool window to a desired location.
As you drag a dockable window, a series of docking markers appear, indicating
valid docking locations. Docking markers appear as a series of large blue
arrows. Move the mouse over a docking marker to preview how the window
would be docked when using that marker. Release the mouse button while
hovering over a marker to use that location.
These markers dock tools to the edge of an existing tool or to
the Machine Edition environment window.
This marker “stacks” the tool overtop an existing tool window,
forming a series of tab-docked windows. You can then switch
between tab-docked tools by clicking the tabs that appear at
the bottom of the tab-docked windows.
GFK-1868Q
Proficy* Machine Edition* 7.50
19
2
Prof icy* Machine Edition*
Getting to Know Machine Edition
Projects and the Navigator
Navigator
The Navigator window organizes and manages your projects.
■
■
■
Use the Navigator to create and manage projects, add targets and
components to your project, set your environment preferences, create scripts,
open editors, create variables, and more.
The Navigator is organized into several tabs. The available tabs depend on
which Machine Edition products are installed and whether a Machine Edition
project is open. For example, the Project and Variables tabs appear only
when a Machine Edition project is open.
Within each tab, items are displayed in a tree of nodes or folders. You can
expand and collapse the tree, just like folders in Windows Explorer.
The following picture illustrates the Navigator prior to any projects being opened.
All the files listed under My Computer are projects that you can access on your
computer. The Samples folder contains sample projects and tutorials.
Want to know more? In the Help Index, look up “Navigator” and choose “Navigator Tool
Window”.
To add a new project, rightclick
My Computer and choose
New.
The Manager tab lists all
projects located on your
hard drive and (if you are
using a Change Management system) under
Change Management.
Use it to create and open
projects, and to manage
projects on a Change
Management system.
or
Select Restore to add an
existing or backed-up
Machine Edition project to
your computer.
A Machine Edition project
must be backed up before it
can be moved to another
computer. To do this, rightclick a project listed under
My Computer and choose
Back Up.
The Utilities tab contains
useful tools for working on
your projects. Available
utilities depend on which
Machine Edition products
are installed.
Navigator Window with Local Project List
20
Proficy* Machine Edition* 7.50
The InfoView tab contains the table of contents for the Help.
GFK-1868Q
Prof icy* Machine Edition*
Getting to Know Machine Edition
To ope n a project in t he Nav i gator
1. In the
Manager tab of the Navigator, right-click an existing project listed
under
My Computer and choose Open.
The project is opened in Machine Edition. The Variables and Project tabs are
added to the Navigator and the nodes change to reflect those components that
make up the project you just opened.
Targets are the hardware
devices and computers that
your finished project will run
on. A project can have multiple
targets.
These nodes represent the
different parts of your
project. They appear
when you add components to a target.
For example, the Control I/O Drivers,
Ladder_Program,
Logic and SFC folders
appear when a Logic
component was added
to Target1 (when using
Logic Developer - PC).
The Options tab contains
option and preference settings for the Machine Edition environment.
The Project tab organizes your project.
Use it to navigate around your project,
and add, delete, and configure the
items that make up your project.
The Variables tab contains all
the variables in your project.
Use it to add, delete, move, and
otherwise manipulate variables.
Navigator Window with an Open Project
GFK-1868Q
Proficy* Machine Edition* 7.50
21
2
Prof icy* Machine Edition*
Getting to Know Machine Edition
Properties and the Inspector
Inspect or
In Machine Edition, practically every object has properties. Properties are
attributes and information about that object. For example, the properties of a box
on an HMI graphical panel include Height, Width, Fill Color, and Outline Color.
The properties of an object are edited in the Inspector window:
■
■
■
To edit an object’s properties, select it with the Inspector open. The Inspector
displays all those properties associated with the selected object.
When a property changes an object’s appearance, you will see the results of
the change immediately in the object’s editor.
To see more properties for an object, select a tab at the bottom of the
Inspector.
If you are ever unsure of the valid
range for a property, hover the mouse
over its current value and look at the
status bar at the bottom of the Machine
Edition window.
This is the
kind of object
you selected.
To edit this property, type
the new value in the box.
To edit this property,
select the new value
To edit this property,
click the
button.
Properties are
organized
much like Windows folders.
Select a tab for more
properties.
Click to expand
the list of subproperties.
Inspector Window
As you select the various properties within the Inspector, the Companion
displays a brief description of the selected property.
Want to know more? In the Help Index, look up “Inspector” and choose “Inspector Tool
Window”.
22
Proficy* Machine Edition* 7.50
GFK-1868Q
Prof icy* Machine Edition*
Getting to Know Machine Edition
Data Watch Lists
The
Data Watch (available only while editing a project) is a debugging tool
that you can use to monitor and edit real-time values of variables defined in your
project. This is useful while working online with a run-time target. With the Data
Watch tool, you can monitor individual variables or user-defined watch lists of
variables. You can change variable values and force the state of discrete
(BOOL) variables. Watch lists can be imported, exported, or saved with a
project.
There are three tabs in the Data Watch tool:
■
■
■
Navigator: Project tab
The Static tab shows variables added to the Data Watch tool.
The Auto tab contains variables selected in the variable list or associated
with the currently-selected instruction in ladder logic.
The Watch List tab contains all variables in the currently selected watch list.
A watch list lets you create and save a separate list of variables to monitor.
You can define more than one watch list, but only one watch list can be
monitored in the Data Watch tool at a time.
Data Watch nodes
Want to know more? In the Help Index, choose “Data Watch List”.
The IEC or Reference
address of variables
mapped to I/O terminals
or Controller memory.
The structure variable Robot1 has
been expanded to
show all of its elements.
The name and value of
each element of the structure variable Robot1 is
shown here, even when
not expanded.
The Static tab contains variables that
you add to the Data
Watch tool.
The Auto tab displays
variables associated
with the item currently
selected in an editor or
tool.
Double-click a value to
change it.
Data Watch Window
A Watch List tab contains all variables
in your project that have been added to
the currently selected Watch list.
To de fi ne a Wa tc h List :
1. Right-click the Data Watch Lists folder and choose New.
2. Double-click the new Watch List to open it in the Data Watch tool.
3. Add variables to the Data Watch as desired.
The changes to the watch list are automatically saved for later use.
GFK-1868Q
Proficy* Machine Edition* 7.50
23
2
Prof icy* Machine Edition*
Getting to Know Machine Edition
Smart Lists
While working in Machine Edition editors, you are frequently required to input
variable names, instruction mnemonics, and other data items. The Smart List
can speed text entry of these items.
This tells you what you need to
enter or select.
This text changes color
based on whether the
entry is valid or invalid.
For example, invalid
entries are red. Valid
entries in the list are
black. Valid typed entries
that are not in the list
appear green; accepting
this entry creates a new
item (in this case, a new
variable).
24
Proficy* Machine Edition* 7.50
As you type in the input box, the list selection jumps to the item that is closest to
what you typed. Press ENTER to create a
new item based on what is typed, or use
the Down arrow to use the selected item.
Smart List Display
For example, if you typed “fill” in the Smart
List, the FillLevel variable would be highlighted. If you want to use an existing variable (in this case, “FillLevel”), use the
Down arrow to select the highlighted item,
then press ENTER. To create a new variable named “fill”, press ENTER without
using the Down arrow.
GFK-1868Q
Prof icy* Machine Edition*
Getting to Know Machine Edition
The Toolchest
Toolchest
The Toolchest (available only while editing a project) is a repository of
preconfigured object templates you can drag into your project. These objects
can be as simple as a single ladder logic instruction, or as complex as a robotic
arm with fully-configured ladder logic and HMI animation.
While Machine Edition comes with a set of preconfigured object templates, you
can create your own. Because you can add as many copies of them as you
want, this can save you hours of development time.
Want to know more? In the Help Index, look up ”Toolchest: an Overview”.
Toolchest items are grouped
into drawers. Select the drawer
you want with this list box.
Within a drawer,
Toolchest items are
organized into folders.
You can drag these logic instructions directly into your ladder
program.
The Ladder, HMI, and SFC
drawers contain simple instructions and functions.
Other drawers contain
fxClasses—definitions for fully
configured objects that you can
also drag into your project.
Toolchest Window
Definitions of most preconfigured objects within the Toolchest are displayed in
the Companion.
GFK-1868Q
Proficy* Machine Edition* 7.50
25
2
Prof icy* Machine Edition*
Getting to Know Machine Edition
The Feedback Zone
Feedback Zone
The Feedback Zone (available only while editing a project) is an interactive
window that displays output information generated by Machine Edition
components. With the Feedback Zone, you can keep track of project
information, locate validity errors within your project, display generated reports,
and more. It is organized into several tabs. Click a message to display more
information about the error in the Companion Window.
Want to know more? In the Help Index, look up “Feedback” and choose “Feedback Zone
Tool Window”.
Press F4 to cycle
through entries in the
Feedback Zone.
In the Build Tab
(shown), Reports
Tab, and References
Tab, pressing F4 also
opens the project
The Build tab displays the status
and results of a validate or download operation. Use this tab to discover and fix any errors you may
have in your project.
The Import tab displays a list of errors and
warnings from an import operation (for
example, errors/warnings are listed when
you import variables from a Controller into
a Machine Edition project).
The References tab displays a list of all the places a selected
variable is used in a project. Click the Reference tab and then
select a variable from the Variable List. You will see a list of all
the places the variable is referenced in your project.
The Reports tab displays a list of
all reports generated during the
current session. Double-click a
report in the list to redisplay it in the
InfoViewer.
The Messages tab tracks and displays
operations that have been completed
in Machine Edition. For example, a
message is added every time you
open a project.
Feedback Zone
26
Proficy* Machine Edition* 7.50
GFK-1868Q
Prof icy* Machine Edition*
Getting to Know Machine Edition
Managing Variables
Variables are named storage spaces for data values defined in Machine Edition
projects. A variable could store the current velocity of a motion Controller motor,
the height of a robotic arm, or any other value that an application needs to keep
track of. Most variables in a project can be shared among various components
and targets, such as View panels and Logic Developer - PC’s ladder logic.
You manage variables in the
Variables tab of the Navigator, also named the
Variable List. Like most items in Machine Edition, you configure variables by
editing their properties in the Inspector.
The values a variable can store depends on its data type. For example, a DINT
data type indicates that the variable can store “Double Integers”, 32-bit values.
The location where a variable’s value is stored is indicated by its data source.
Typically, a variable’s value is either stored internally in the target’s memory or is
retrieved (and sent) to external Controller hardware, via an I/O terminal or other
connection. Available data types and data sources depend on the target type
and (if applicable) components added to the target.
You can also use arrays and structure data types in Machine Edition projects. An
array is a series of variable elements with identical data types, referenced by a
0-based index (as in “MyArray[3]”). A structure data type is a group of variable
elements that may or may not have the same data type, referenced by the name
of each element (as in “MyStructure.MyElement”). Custom structure data types
are created with fxClasses in the Toolchest.
Want to know more? In the Help Index, look up “STRUCTURE data types”.
Property Columns
In addition to the Inspector, with the three buttons at the top of the Navigator, you
can edit variable properties in a spreadsheet-like column view.
Click to open and close the property column display. This button is available
only in the Variables tab.
Click to dock and undock the Navigator window. Undocking the Navigator
(that is, making it work like an Editor window) can make it easier to work with
properties in the column view.
Click to display a list of available property columns. Double-click a property
to add it to the current set.
GFK-1868Q
Proficy* Machine Edition* 7.50
27
2
Prof icy* Machine Edition*
Getting to Know Machine Edition
When opened, the Navigator’s property columns view consists of a grid of cells:
This grey box indicates the
item whose property you are
editing.
This black box indicates that
the column supports “incremental dragging”. Click and
drag the box downwards to fill
in the cells underneath with
consecutive values, based on
The Navigator’s Property Columns view
Variable Rep ort s
Cells for properties that do not
apply to an item are grayed
out.
While you can generate reports on many things in Machine Edition, they are
especially useful for the Variable List. Among the available reports are:
■
■
■
■
All variables by name, filtered or unfiltered.
Cross-references to variables (that is, the places they are used in the
project).
All forced variables (Logic Developer - PC and Logic Developer - PLC only).
Unused variables (that is, variables with no references anywhere in the
project). The unused variables report also has a link that lets you delete all
unused variables from the project at once.
Reports are displayed as HTML pages in the InfoViewer. To generate a report,
click anywhere in the Variables tab then, on the File menu, select Report.
■
■
■
■
■
■
■
28
Proficy* Machine Edition* 7.50
Want to know more about Variables? Look up the following in the Help Index:
For information on variables in general, choose “Variables: an Overview”.
For information on variables in View, choose “Variable support in View Developer”.
For information on variables in QuickPanel projects, choose “Variable support in QuickPanel
applications”.
For information on variables in Logic Developer - PC, choose “Variable support in Logic
Developer - PC”.
For information on variables in Logic Developer - PLC, choose “Variables in Logic Developer
- PLC vs. Memory in GE IP Controllers: an Overview”.
For information on variables in Motion Developer, choose “Variable support in Motion
Developer”.
For information on importing variables from other applications or database files, choose one
of the “Importing Variables...” topics.
GFK-1868Q
Prof icy* Machine Edition*
Machine Edition Projects
MACHINE EDITION PROJECTS
During development, your automation application is named a project. Each
Machine Edition project is made up of targets and (sometimes) components. A
target represents the hardware platform where the finished project runs, such as
a Windows XP computer, a QuickPanel View/Control unit, a motion Controller, or
a QuickPanel unit. Different Machine Edition products support different target
types. Targets are often further subdivided into models. Components add
specific capabilities to a target. Available components depend on the target type,
model, and what Machine Edition products you have installed.
For example, with View, you can you add an HMI component to Windows PC
and QuickPanel View/Control targets, used for creating human-machine
interfaces. With Logic Developer - PC, you can add a Logic component to
Windows PC and QuickPanel View/Control targets. You can then create ladder
logic to make a PC act as a Controller. QuickPanel View targets do not support
logic; therefore, you cannot download a project that contains logic to one.
With Motion Developer, you can program motion Controllers from your PC. Each
motion device programmed by Motion Developer is represented by a separate
Motion target. Because motion targets have no additional capabilities, they do
not require adding components.
Want to know more? In the Help Index, look up “projects” and choose “Machine Edition
Projects: an Overview”.
Sharing Projects between Machine Edition
Workstations
If your site has multiple Machine Edition workstations connected through a
network, you can use the
Shared Projects folder to work on the same set of
projects. Projects under the Shared Projects folder are stored in a directory you
specify, typically a shared directory on the network.
No access or version control is applied to the Shared Projects folder. If multiple
users open the same project at the same time, some changes may be lost.
Note: Shared Projects and Shared Variables are two completely different and
separate features. For information on Shared Variables (which implement proxy
variables between targets in different projects), see “PLC Access I/O” on
page -83.
Want to know more? In the Help Index, look up “Shared Projects”.
GFK-1868Q
Proficy* Machine Edition* 7.50
29
Prof icy* Machine Edition*
2
Machine Edition Projects
Running a Sample Project (View/Logic
Developer - PC)
If you are using View or Logic Developer - PC, we’ve provided some sample
projects that show basic operations of Machine Edition. Take a few minutes to
complete the following steps and learn the basics of project development in
Machine Edition.
■
For a more detailed example of creating projects, in the Help Index, look up
“Tutorial” and choose one of the topics listed there.
To run a sam ple project
1. Run Machine Edition from the Start menu | All Programs | Proficy | Proficy
Machine Edition | Proficy Machine Edition.
2. In the
Manager tab of the Navigator, double-click one of the sample
applications listed under the
My Computer folder.
Sample applications include the following:
30
■
Alarm Trends: an HMI application that demonstrates alarms and charts.
■
Animation Features: an HMI application that depicts the various types of
animation available in View.
■
Brewery: an HMI and logic brewery application that runs on a Windows PC
target.
■
Car Wash: an HMI and logic application that runs on a Windows PC target.
This application is built in an SFC document.
■
ControlStation HMI Features: an HMI and logic application that runs on a
Windows PC target. This application also shows some web documents.
■
QP Control 6 inch Brewery: an HMI and logic brewery application that runs
on a QuickPanel Control unit. (Projects containing a logic component cannot
be downloaded to a QuickPanel View unit, because QuickPanel View units
do not support logic.)
■
QP Control 6 inch Ventilation: an HMI and logic application that runs on a
QuickPanel Control unit. This application runs a four-zone ventilation logic
system. It is to be used with the QuickPanel Control unit Tutorial. (Because
QuickPanel View units do not support logic, projects with a logic component
cannot be downloaded to a QuickPanel View unit.)
■
ST - Lunar Lander: an HMI and logic application that runs on a Windows PC
target. This project demonstrates the Structured Text (ST) language and its
interaction with User Defined Function Blocks (UDFBs).
Proficy* Machine Edition* 7.50
GFK-1868Q
Prof icy* Machine Edition*
Machine Edition Projects
Tutorials include
■
Animation: an HMI application that illustrates and provides details on the
various animations that you can use in your HMI.
■
AppExec: an HMI application that demonstrates the AppExec Script function.
■
Keystrokes: an HMI application that displays the analog values associated
with the keys on your keyboard.
■
Logging: an HMI application that demonstrates how to log production data to
an ASCII text file.
■
Recipes: an HMI application that shows how one would load and modify
recipes.
■
Scripting: an HMI application that demonstrates some of View’s scripting
capabilities.
3. Browse through the project in Machine Edition.
Open the project’s graphical panels, ladder logic, and SFCs (if they exist) in their
respective editors. To open an editor, right-click the appropriate node in the
Project tab of the Navigator and choose Open.
Also, take a look at the properties of the various nodes and objects. To view an
object’s properties, open the Inspector window, and then select an object.
4. In the newly opened project, press F9 to validate, download, and run the sample
application.
The F9 key is a shortcut for the Run command which automatically starts View
Runtime and the Controller.
The sample application should now be running in both View Runtime and the
Controller. View Runtime appears, displaying the first panel of the project’s HMI.
You can see the real-time status of the logic by going online to the Controller.
To go online to t he Cont rolle r
If you have chosen a project that contains logic and/or an SFC document, you
can go online to the application and watch the logic being executed.
1. Minimize the Runtime window (but do not close it) and return to Machine Edition.
2. In the
Project tab of the Navigator, right-click the Target node and choose
Go Online.
You are now online to the Controller; that is, you are working with the application
while it is running. The Controller is the part of the Runtime that solves logic and
SFCs.
GFK-1868Q
Proficy* Machine Edition* 7.50
31
2
Prof icy* Machine Edition*
Machine Edition Projects
3. In the
Project tab of the Navigator, open the Ladder Editor by double-clicking
Ladder Program node or open the SFC Editor by double-clicking the
SFC node.
In the editor, you can watch the logic being solved as the Controller operates. To
start and stop Runtime and the Controller, right-click the target, point to
Online Commands, and then click Start/Stop Runtimes. To go offline from the
Controller, right-click the target, and then click Go Offline.
the
Developing a Machine Edition Project
The first thing to decide when you create a Machine Edition project is where the
project will run after it is developed. That is, on what type of target hardware it
will run.
For View and Logic Developer - PC, targets can be a Windows PC computer
(either the one you are developing the project on, or a remote one that you
connect to through a network), or a QuickPanel View/Control unit.
For View alone, your target can also be a conventional QuickPanel unit.
For Logic Developer - PLC and Logic Developer - State, your target is a
PACSystems, Series 90, or VersaMax Controller. You can also configure remote
I/O targets that represent a variety of remote I/O adapters and their associated
I/O modules. See GFK-1918 Getting Started Logic Developer - PLC.
If you are using Motion Developer, the choice is easy—determine whether your
motion hardware is a motion Controller/drive or a drive-only device (see page
101).
After you’ve decided on the target, you need to determine which components
your project will include: HMI (with View) and/or Logic (with Logic Developer PC). Note that ViewStations do not support Logic components. A project can
have multiple targets of different types with various components running on each
target. In some cases, targets can be converted from one type to another. For
example, you can convert a Windows XP target to and from a QuickPanel View
target.
Want to know more? In the Help Index, look up “Targets: an Overview”.
To crea te a nd de velop a projec t
The following procedure introduces the general steps involved in creating a
project using a template, and downloading a project to a target computer.
1. Start Machine Edition from the Start menu | All Programs | Proficy | Proficy
Machine Edition | Proficy Machine Edition.
32
Proficy* Machine Edition* 7.50
GFK-1868Q
Prof icy* Machine Edition*
Machine Edition Projects
2. Create a project using a template.
In the
Manager tab of the Navigator, right-click
My Computer and choose
New. The New Project dialog box appears.
If you are using shared projects, you can also add new projects under the
Shared Projects folder. Or, if you are working on a Change Management system,
you can add new projects to the Machine Edition folder under the Server.
3. In the New Project dialog box, enter a name for the new project, select a
template, and then click OK.
A description of the template appears below your selection. You can click
hypertext links in the description for details on the template components.
At this point, you need to know the type of target hardware to which your project
will download, as this will determine which template you choose. In some project
templates (such as the “View/Control” template), you can select this as one of
several parameters within an HTML page on the template dialog box.
The project is opened in Machine Edition and the Navigator changes to reflect
those components that make up the project you just created.
Want to know more? In the Help Index, look up “templates” and choose “Creating a New
Machine Edition Project” or “Creating a new project under a Change
Management system”.
4. In the Variable List, create variables for your application.
In the
Variables tab of the Navigator, right-click the Variable List node, point to
New Variable, and choose the type of variable you want to create.
By default, the
Variable List node filters out all system variables. System
variables are created automatically when you add components to Windows PC,
QuickPanel View/Control, QuickPanel, or GE IP Controller targets. To display all
variables including system variables, right-click the Variable List node, point to
Filter By, and choose No Filter.
Want to know more? In the Help Index, look up “Variables: an Overview”.
5. Create your application.
With Logic Developer - PC, add logic (Ladder, FBD, IL, ST, SFC) to your project,
and then configure a control I/O driver to model your hardware. If the template
you chose did not include a Logic component, add one now—right-click the
target, point to Add Component, and choose Logic. (View-only targets do not
support logic.)
■
GFK-1868Q
In the
Project tab of the Navigator, under the Logic folder, open the Ladder
Editor by double-clicking the
Ladder Program node.
Proficy* Machine Edition* 7.50
33
2
Prof icy* Machine Edition*
Machine Edition Projects
■
Drag ladder instructions from the
Toolchest into the editor. You can find
ladder instructions in the PC Ladder Instructions drawer of the Toolchest.
■
Assign variables to instructions. You can do this with the Smart List, which
appears when you insert or double-click an instruction. Or, drag a variable
from the
Variables tab of the Navigator and drop it on the instruction you
want it mapped to.
You can add additional logic blocks (ladder subroutines, FBD, IL, ST) and
organize your logic with SFC.
■
Want to know more? In the Help Index, look up “Ladder Instructions: an Overview (PC)”.
With View, you can create the graphical panels and animation for your project. If
the template you chose did not include an HMI component, then add one now—
right-click the target, point to Add Component, and choose HMI. (If a target has
both an HMI and a Logic component, you will typically create the Logic
component first.)
■
In the
Project tab of the Navigator, open the Panel Editor by doubleclicking a
Panel node.
Use the Graphical Panel toolbar to create your HMI and/or drag graphical
objects from the Toolchest onto a panel. You can find a set of fully-configured
objects (complete with animation) in various Toolchest View Expert Objects
drawers.
With Motion Developer, begin by running the Motion Expert wizard.
■
■
If necessary, open the “Main Wizard” home page by right-clicking the Motion
target and choosing Main Wizard.
■
In the wizard page, click Motion Expert and follow the instructions on screen.
For more information on using wizards, see page 106.
6. If necessary, configure the I/O hardware connections for your project.
■
For Logic Developer - PC, set up Control I/O in the
Control I/O Drivers
folder (in the
Project tab of the Navigator). To add a driver, right-click the
Control I/O Drivers folder and choose New Driver. Use the Control I/O tool to
configure your drivers. Map variables to I/O terminals.
Want to know more? In the Help Index, look up “Control I/O Tool: an Overview”.
■
34
Proficy* Machine Edition* 7.50
For View, set up PLC Access I/O in the
PLC Access Drivers folder. To add
a driver, expand the PLC Access Drivers folder, right-click View Native
Drivers, and click New Driver. Configure the drivers in the Inspector window.
On Windows PC targets, you may want to set up OPC I/O in the
OPC
Client folder.
GFK-1868Q
Prof icy* Machine Edition*
Machine Edition Projects
7. When your project is complete; validate, download, and run your project by
pressing the F9 function key.
Machine Edition saves the project, performs a validation, builds the run-time
files, and attempts to establish a connection to the target computer.
Validating and Downloading a Project
During project development, you will go through the validation and download
processes several times. The validation process checks the project for errors. If
the project contains errors, they are listed in the Build tab of the
Feedback
Zone.
■
All errors must be fixed before the download process can proceed. Warnings
are also listed in the Feedback Zone, but they do not prevent the download
from starting.
When fixing project errors, use the F4 function key to scroll through errors in the
Feedback Zone, jumping to their locations in the project.
The download process involves two steps. The first step creates (or “builds”) all
the run-time files necessary for a target to perform its role in a completed project.
The second step downloads those files to the target devices or computers.
■
■
■
For Motion Developer, the easiest way to set up the motion control device for
downloading is with the Set Communication Parameters wizard. Open the
Main Wizard page for the target (right-click the target and select Main
Wizard). Then, point to Target Configuration and click Communication
Parameters. Click Finish when you are done.
To download a View or Logic Developer - PC project to the Windows PC
computer on which you are developing (a local target), ensure that the target
property Computer Address is set to “.” (without the quotation marks).
Otherwise—for remote targets—enter the IP address or computer name of
the remote computer you want to download to, in the Computer Address
property.
To download a QuickPanel project, ensure that the target property Computer
Download Port is set to the applicable COM port.
Additional basic information on setting up Windows PC and QuickPanel
View/Control targets follows.
Pr eparing a R emot e Windows PC ta rget f or Downloading
The following steps need to be completed on a remote Windows PC target
computer before you can download a project to it.
1. If you are downloading to another Windows PC computer, ensure that the run-
time files are installed on that device.
GFK-1868Q
Proficy* Machine Edition* 7.50
35
2
Prof icy* Machine Edition*
Machine Edition Projects
QuickPanel View/Control targets are shipped with the run-time files preinstalled.
If you are using your own Windows PC computer, you will have to install the runtime files yourself from the Machine Edition installation DVD (see page 4).
2. Share the Machine Edition installation directory with the development computer
that contains the project files.
In the Windows PC Explorer, navigate to the Proficy Machine Edition folder,
right-click it and choose Sharing. Click Shared As and in the Share Name field,
enter Proficy Machine Edition.
3. Ensure you have the proper permissions to download files to the target
computer.
In Windows PC, open the Control Panel, click Administrative Tools, and then
click Computer Management. Expand “System Tools” and then expand “Local
Users and Groups”. Select the Users folder. In the right pane, double-click the
Guest user account. In the Guest Properties dialog box that appears, clear the
Account is Disabled check box.
4. Within your Machine Edition project, specify the IP address or computer name of
the remote Windows PC target in the Computer Address target property. This
enables Machine Edition to locate and connect to the Windows PC target
computer.
Type the IP address or the
computer name of the
remote Windows PC target
to which you want to download your project files.
Want to know more? In the Help Index, look up “Preparing Windows PC targets for
downloading”.
Pr epari ng a Qui ck Pa nel Vi ew/ C ontrol ta rget f or downloading
The following steps need to be completed on a QuickPanel View/Control target
before you can download a project to it. If you are not physically connected to
the QuickPanel View/Control unit but want to test your project, you can
download the project to your local computer by setting the Use Simulator target
property to True. You cannot download a project that contains a logic component
to a QuickPanel View target, because they do not support logic.
36
Proficy* Machine Edition* 7.50
GFK-1868Q
Prof icy* Machine Edition*
Machine Edition Projects
1. Physically connect the QuickPanel View unit to the Ethernet network. This step
may require a network administrator.
2. Within your Machine Edition project, specify the IP address of the QuickPanel
View/Control unit in the Computer Address target property.
To find the IP address of a QuickPanel View/Control unit, double-tap the System
Information icon located on the unit’s desktop.
By default, the QuickPanel View/Control unit uses a DHCP (Dynamic Host
Configuration Protocol) IP address. This means that the IP address is
dynamically assigned by the Ethernet network server using DHCP. If you want to
use a fixed IP address, you must manually set the IP address on the unit.
Want to know more? In the Help Index, look up “Preparing QuickPanel View/Control targets
for downloading”.
Type the IP address of the
QuickPanel View/Control
unit to which you want to
download your project files.
Testing a View Project
The following steps introduce you to the Quick Test feature. Quick Test is similar
to a preview: with Quick Test, you can quickly see the results of any changes
you’ve made to a graphical panel without having to download your entire project.
NOTE
The Quick Test feature is not available on QuickPanel targets.
Before you can use Quick Test, your project must have been downloaded at
least once to the target computer. If you want to Quick Test a graphical panel
from a QuickPanel View/Control project, you must set the target’s Use Simulator
property to True and perform at least one download after changing the setting.
To Quic k Test change s made to a graphica l pa nel
1. Ensure that you’ve downloaded the HMI to the target computer at least once.
2. If you have not already done so, open the graphical panel you want to test.
3. Right-click in the panel and choose Quick Test.
View Runtime appears with a preview of the graphical panel.
GFK-1868Q
Proficy* Machine Edition* 7.50
37
Logic Developer - PC
3
Logic Developer - PC
Logic Developer - PC is Machine Edition’s PC Control product, where you edit a
project’s logic component. With Logic Developer - PC you create control
programs using standard IEC 61131-3 editors in a graphical environment. The
programs you create are downloaded to and executed on the PC Logic
Controller. You interface to a plant or process through the I/O system of your
choice; Logic Developer - PC supports a wide range of industry standard
hardware.
Logic Developer - PC supports Windows 7 and Windows XP (“Windows PC” for
short), and QuickPanel Control/View targets. All user-defined logic programs are
contained in the
Logic folder, including the following:
Navigator: Project tab
■
Sequential Function Chart (SFC) editor (see page 41)
■
Ladder Program (see page 45)
■
Instruction List Blocks (see page 49)
■
Structured Text Blocks (see page 52)
■
Function Block Diagram (see page 55)
The following run-time elements are included with Logic Developer - PC:
■
Control I/O Drivers (see page 62)
■
PC Logic Controller (on target computer) (see page 65)
TIP
GFK-1868Q
Logic Developer - PC Web Access (see page 59)
■
User-defined
folders can be added to the Logic folder or to another user-defined
folder to organize your logic. A user-defined folder can contain any type of logic block
contained in the logic folder, except ladder (of which there can be only one).
Proficy* Machine Edition* 7.50
39
3
Logic Developer - PC
To crea te a pr oje ct t hat includes a logic c omponent
1. In the
Manager tab of the Navigator, right-click
New.
The New Project dialog box appears.
My Computer and choose
2. In the Project Name box, enter a name for your project.
3. From the Project Template list, choose a template that includes a logic
component.
A preview of what each template includes is displayed as you select different
templates.
4. Click OK.
Your new project is created and the Project tab opens in the Navigator.
To add a logi c c omponent to an ex is ti ng project
• In the
Project tab of the Navigator, right-click a target, point to Add
Component and click Logic.
The
Logic folder with an empty ladder program and SFC component is added
to your project.
To add a user -def i ned fol der t o y our proj ect
1. Ensure that your project contains a logic component (see above).
2. Right-click the
Logic folder or a
user-defined folder, point to New, and click
Folder.
The new folder appears in the
Project tab of the Navigator in alphabetical
order.
3. (Optional.) Enter a name for the new folder.
40
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
SFC Editor
SFC EDITOR
SFC logic is a graphical language for organizing the sequential execution of
control logic. The SFC editor is an easy-to-use graphical tool for editing
sequential function charts in the Machine Edition environment. With the SFC
editor, you can work on a disk copy of a sequential function chart (offline) or
monitor the execution of an SFC running in the Controller (online). You can also
configure the appearance and behavior of the SFC editor.
Sequential Function Chart
Navigator: Project tab
SFC nodes
An SFC is much like a flow chart; it is a high-level control program that organizes
detailed blocks of logic into a state-like flow. In general, an SFC consists of steps
alternating with transitions. A transition can be a BOOL variable or a Structured
Text statement, which resolves to a BOOL value. Each step represents a state
that the program is in until the transition following it allows execution to proceed
to the next step. Each step contains actions that are user-defined sections of
ladder, IL, ST, or FBD logic. The actions in a step are executed in the order they
are listed and are repeated each Controller scan while the step is active. Each
action in a step has a qualifier associated with it that determines when and how
the action is executed.
An SFC document is a grid of cells. Each cell can contain an instruction. The
instruction set includes steps, transitions, branches, parallels, and jumps.
An SFC can be expanded by adding macros. Each macro is a special SFC
document that can be referenced any number of times from its SFC document or
other macros.
Want to know more? In the Help Index, look up “macro” and choose “SFC Macro”. You can
also look up “SFC Tutorial” in the online help Index. This tutorial takes
you step-by-step through the creation of a Sequential Function Chart
that controls traffic signals.
To add a new SFC
1. In the
Project tab of the Navigator, right-click the
Logic folder or a
userdefined folder, point to New, and click SFC.
The new
SFC appears under the
Logic folder or a user-defined folder in
alphabetical order.
2. (Optional.) Enter a unique name for the new SFC.
GFK-1868Q
Proficy* Machine Edition* 7.50
41
3
Logic Developer - PC
SFC Editor
To ope n an SFC or m ac ro for edit ing
• In the
Project tab of the Navigator, under the
Logic folder or under a
user-defined folder, double-click an
SFC or
macro node.
The SFC editor opens with the document ready for editing.
To crea te a ne w SFC m acr o
1. In the
Project tab of the Navigator, under the
user-defined folder, right-click an
SFC or
Logic folder or under a
macro node and click New.
2. (Optional.) Enter a unique name for the new macro.
Your new macro appears as a child node of the SFC or macro node you started
with.
Working with the SFC editor - Offline
The SFC editor interacts with the Machine Edition tools to provide maximum
flexibility when editing a program. The following picture illustrates some of the
operations you can perform.
Configure instructions and their
associated variables in the
Inspector.
Call a macro with
a Macro Step
instruction.
Use the Variable
List to create
variables then
drag them to
instructions in
the SFC editor.
The Companion provides
help on anything you click.
42
Proficy* Machine Edition* 7.50
Insert instructions, rows, and
columns with the
SFC toolbar.
Drag instructions
from the SFC
drawer of the
Toolchest to the
SFC editor.
Right-click a
blank cell to start
editing.
Locate all
instances of a
variable (References) or syntax
errors (Build).
GFK-1868Q
Logic Developer - PC
SFC Editor
T o ins ert a n SFC i n st ruct i o n
1. In the SFC editor, right-click a blank cell and click Place Instruction.
2. Choose an instruction mnemonic from the smart list that appears and press
ENTER to finish.
You can set the SFC editor options to automatically assign default variables to
instructions or to let you choose and create your own.
To Quic k E di t an SFC
• In the SFC editor, click a blank cell and type instruction mnemonics separated by
operators (see the following table). Press ENTER to finish.
Each mnemonic specifies one or more instructions. Each operator moves the
location of the currently selected cell. Default variables are assigned when Quick
Editing an SFC.
SFC Operators
GFK-1868Q
To ...
Use ...
move right one cell
move left one cell
move down one cell
stay on current cell
+
;
/
Proficy* Machine Edition* 7.50
43
3
Logic Developer - PC
SFC Editor
Working with the SFC editor - Online
In the SFC editor, you can view the execution of an SFC as it happens. The
following picture illustrates this capability.
Active steps
and transitions are
highlighted in
bold.
Power flow in the
associated ladder program
(actions) is indicated in bold
while actions are
executed.
Many actions
can be viewed at
once.
Right-click
any BOOL to
turn or force it
The References
tab of the Feedback Zone lists all
instances of a variable. Click an entry
to locate it in an
editor.
Use the Data
Watch to monitor or change
data values in
real time.
T o go o n l i n e to t h e Co n t rol le r’ s S F C
• In the
Project tab of the Navigator, right-click the target and click Go
Online. (Before you can go online to the Controller, you must first download the
project.)
The Controller’s SFC appears in the SFC editor. When the Controller is running,
active steps and transitions are graphically indicated.
44
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Ladder Editor
LADDER EDITOR
Ladder logic may be the most popular language in use today for creating control
programs. The ladder editor is a graphical tool for editing ladder programs in
Machine Edition. With the ladder editor, you can work on a disk copy of a ladder
program (offline) or with a live program as it runs in the Controller (online). You
can also configure the appearance and behavior of the editor under the
Options tab of the Navigator.
Ladder Program
A ladder program is composed of rungs of ladder logic instructions that execute
sequentially from left to right, top to bottom. The instruction set includes standard
IEC 61131-3 functions supplemented by a large library of advanced and I/O
specific functions. Along with rungs and instructions, a ladder program contains:
Navigator: Project tab
■
Labels: Each default (START and END) or user-defined
rung providing an entry point for program execution.
■
Subroutines: Each user-defined
subroutine is a separate, reusable
section of logic that can be called from anywhere in a ladder program.
■
Actions: Each
action is a separate block of logic that can be
referenced in a Sequential Function Chart.
ladder logic nodes
label is a
Tip: You can also create User-Defined Function Blocks (UDFBs). Each UDFB is
a callable subroutine to and from which you can pass parameters.
Want to know more? In the Help Index, look up “ladder” and choose “Ladder Program: an
Overview”. Also look up “UDFB” and choose “User-defined Function
Blocks: an Overview”.
To ope n a ladder progra m for e diting
• In the
Project tab of the Navigator, under the
Ladder_Program node.
Your ladder program opens in the ladder editor.
Logic folder, double-click the
To loc ate a la bel
• In the
Project tab of the Navigator, under the
Logic folder, under the
Ladder Program folder, double-click a
label node.
Your ladder program, subroutine or action opens in a ladder editor window with
the label selected.
GFK-1868Q
Proficy* Machine Edition* 7.50
45
3
Logic Developer - PC
Ladder Editor
To crea te a ne w subroutine or a cti on
1. In the
Project tab of the Navigator, under the
Logic folder, under the
Ladder Program folder, right-click the
Subroutines or
Actions node and
click New.
2. (Optional.) Enter a unique name for the new subroutine or action.
An empty
subroutine or
action, labeled with the name you entered, is
created. Double-click the node to open it for editing. You can add ladder logic to
the subroutine or action as required.
Working with the ladder editor - Offline
The ladder editor interacts with all of the Machine Edition tools to provide
maximum flexibility when editing a program. The following picture illustrates
some of the operations you can perform.
Insert rungs and
common instructions with the ladder Instruction
toolbar.
Click a shunt and
type mnemonics
to insert instructions (QuickEdit).
Drag variables to
instruction parameters to configure
them.
Edit descriptions
in place for
rungs, variables,
and your ladder
program.
Drag branches
around instructions to create parallel execution
paths.
Drag instructions
from the PC Ladder Instructions
drawer of the
Toolchest.
Display subroutines and actions
in separate editor
windows.
Locate all
instances of a
variable (References) or syntax
errors (Build).
The Companion
automatically provides information
on what you click.
To ins ert a rung
• In the ladder logic, right-click a rung, shunt, label or description and click Insert
Rung.
An empty rung is inserted. You can set the editing options for the ladder editor so
that rungs are inserted either before or after the current selection.
46
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Ladder Editor
To Quic k Edit la dder logic
• In the ladder logic, click a rung and type instruction mnemonics separated by
semicolons, and then press ENTER.
The instructions specified by the mnemonic string you entered are inserted, in
order, on the rung. You can enter mnemonics followed by variable names if you
want to assign instruction parameters while Quick Editing.
Example: Add a Normally Open Contact (NO) instruction followed by a Coil
(OUT) instruction and assign the variables MySwitch and MyCoil to these
instructions respectively.
NO MySwitch; OUT MyCoil
Working with the ladder editor - Online
With the ladder editor you can go online to a ladder program being run by the
Controller (page 65). While online, you can view the power flow through the
ladder logic and watch data values change in real time. You can also edit the
ladder program, just as you would while offline, with the following restrictions:
■
Labels, subroutines, and actions cannot be deleted while online.
■
Only one rung can be changed before writing the changes to the Controller.
The following picture illustrates the ladder editor while online to the Controller.
Online status is
indicated by the
color of the target
icon.
New or edited
rungs are indicated with alternately colored and
bolded lines until
you Write
Changes.
Power flow is
indicated with
bold colored
lines.
GFK-1868Q
Lightning bolts in
each corner indicate the Controller’s status and
change to reflect
fault conditions.
Data values are
displayed in real
time as they
change each scan
on the Controller.
Use the Data
Watch to view or
set data values for
any variable in
your project.
Proficy* Machine Edition* 7.50
47
3
Logic Developer - PC
Ladder Editor
To go online to t he Cont rolle r’s ladder progr am
• In the
Project tab of the Navigator, right-click the
target and click Go
Online. (Before you can go online to the Controller, you must first download the
project.)
The Controller’s ladder program appears in the ladder editor. When the
Controller is running, power or state flow is graphically indicated and data values
updated.
To write a c hanged rung to t he Cont rolle r
• From the Controller menu, choose Write Changes. (The Controller menu is
available only when the ladder editor is selected.)
The Controller’s ladder program is updated with the single altered rung.
48
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Instruction List Editor
INSTRUCTION LIST EDITOR
IL logic is one of four languages specified by the IEC 61131-3 standard. The IL
editor is an easy-to-use, intelligent, free-form text editor for editing IL blocks in
the Machine Edition environment. With the IL editor, you can work on a disk copy
of an instruction list (offline) or monitor the execution of an IL block running in the
Controller (online). You can also configure the appearance and behavior of the
editor under the
Options tab of the Navigator.
Instruction List
IL is a low-level language composed of basic and advanced Math instructions
that execute sequentially from top to bottom. IL blocks can also contain labels
providing entry points for program execution. In its simplest form an IL can:
1. Load a data value (operand) into the accumulator.
2. Perform an operation on the accumulator, saving the result in the
Navigator: Project tab
accumulator.
IL block nodes
3. Store the accumulator’s value to memory (a variable).
4. Do another accumulator load or operation, and so on.
Want to know more? In the Help Index, look up “IL” and choose “IL Editor”.
To ope n an IL block f or edit ing
• In the
Project tab of the Navigator, under the
Logic folder or under a
user-defined folder, double-click an
IL block node.
Your IL block opens in the IL editor.
To crea te a ne w IL block
1. In the
Project tab of the Navigator, right-click the
Logic folder or a
defined folder, point to New, and click Instruction Language.
user-
2. (Optional.) Enter a name for the new IL block.
Your new IL block appears as a child node of the Logic folder or a user-defined
folder.
NOTE
GFK-1868Q
IL blocks can be executed only when called as Actions from an SFC.
Proficy* Machine Edition* 7.50
49
3
Logic Developer - PC
Instruction List Editor
Working with the IL editor - Offline
The IL editor interacts with the Machine Edition tools to provide maximum
flexibility when editing a program. The following picture illustrates some of the
operations you can perform.
Drag variables to the IL
editor to complete IL statements.
Multiple-line
block comments to document your IL
block.
Copy and
paste one or
more IL statements from
the IL editor to
other sections
or IL blocks.
In-line comments for individual IL
statements.
Begin typing
for a Smart
List to appear
(see page 24).
Locate all
instances of a
variable with
the References tab of
the Feedback
Zone.
The Companion automatically provides
information on
what you click.
To ins ert a n IL inst ruct ion
1. In the IL editor, begin typing.
A smart list appears containing any items (labels, mnemonics, or variables) that
are applicable at the current cursor position.
2. Enter or choose from the list the mnemonic you want.
50
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Instruction List Editor
Working with the IL editor - Online
In the IL editor, you can view the execution of an IL block as it runs. This is
illustrated in the following diagram.
Online status
is indicated by
the color of
the target
icon.
The grey
background
indicates that
the editor is
online to the
Controller and
is read-only.
Variable types
and their data
values are displayed in real
time as they
change each
scan on the
Controller.
Use the Data
Watch tool to
view or set
data values
for any variable in your
project.
Right-click any
BOOL variable to force it
On/Off or to
turn it On/Off.
T o go o n l i n e to t h e Co n t rol le r’ s I L
1. In the
Project tab of the Navigator, right-click the
target and click Validate
(F7).
2. Right-click the target and click Download (F8).
3. Right-click the target and click Run (F9).
4. Right-click the target and click Go Online (CTRL+F11).
The Controller’s IL block appears in the IL editor as read-only and with a grey
background. In the IL editor, you can monitor the values of a variable, by clicking
the variable. You can also change or force BOOL variable states.
GFK-1868Q
Proficy* Machine Edition* 7.50
51
3
Logic Developer - PC
Structured Text Editor
STRUCTURED TEXT EDITOR
ST logic is one of four languages specified by the IEC 61131-3 standard. The ST
editor is an easy-to-use, intelligent, free-form text editor for editing ST blocks in
the Machine Edition environment. With the ST editor, you can work on a disk
copy of a structured text block (offline) or monitor the execution of an ST block
running in the Controller (online). You cannot edit an ST block online.
Structured Text
ST is a high-level language composed of basic and advanced Math instructions.
ST blocks can be executed as Actions called from SFC Steps, or when called as
a subroutine from other ST blocks or ladder programs.
Navigator: Project tab
ST block nodes
If there is an ST block named ‘MAIN’, it executes after the SFC programs. That
is, after downloading a Logic Developer - PC application, the execution of every
scan begins with the ladder program, then any SFC programs, and then the ST
block named MAIN.
ST supports a timer, arrays, bitwise access, strings, and User Defined Function
Blocks (UDFBs—callable subroutines to and from which you can pass
parameters). The Return keyword causes an early exit from a subroutine.
Want to know more? In the Help Index, look up “ST Editor (PC)” or look up “UDFB” and
choose “User Defined Function Blocks: an Overview”.
To ope n an ST block f or editing
• In the
Project tab of the Navigator, under the
Logic folder or under a
user-defined folder, double-click an
ST block node.
Your ST block opens in the ST editor.
To crea te a ne w ST block
1. In the
Project tab of the Navigator, right-click the
defined folder, point to New, and click ST Block.
Logic folder or a
user-
2. (Optional.) Enter a name for the new ST block.
Your new ST block appears under the Logic folder or under a user-defined
folder.
52
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Structured Text Editor
Working with the ST editor - Offline
The ST editor interacts with the Machine Edition tools to provide maximum
flexibility when editing a program. The following picture illustrates some of the
operations you can perform.
Multiple-line
block comments to
document
your ST
block.
Drag variables
to the ST editor to complete ST
statements.
Hover over a
variable with
the mouse
pointer to see
its data type.
Copy and
paste ST
statements
from the ST
editor to other
sections or ST
blocks.
In-line comments for individual ST
statements.
The Companion automatically provides
information on
what you click.
Locate all
instances of a
variable in the
References
tab of the
Feedback
Zone.
To ins ert a n ST i nst ruct ion
1. In the ST editor, begin typing. To see a list of valid variables, right-click anywhere
and click Insert Variable. Choose a variable from the list that appears, then
press ENTER.
2. To obtain a list of valid mnemonics, right-click anywhere and click Insert
Keyword. Choose a keyword from the list that appears, then press ENTER.
GFK-1868Q
Proficy* Machine Edition* 7.50
53
3
Logic Developer - PC
Structured Text Editor
Working with the ST editor - Online
In the ST editor, you can view the execution of an ST block as it runs. This is
illustrated in the following diagram.
The grey
background
indicates that
the editor is
online to the
Controller and
is read-only.
Online status
is indicated by
the color of
the target
icon.
Variable types
and their data
values are displayed in real
time as they
change each
scan by the
Controller.
Use the Data
Watch tool to
view or set
data values
for any variable in your
project.
Right-click any
BOOL variable to force it
On/Off or to
turn it On/Off.
T o go o n l i n e to t h e Co n t rol le r’ s S T
1. In the
Project tab of the Navigator, right-click the
target and click Validate
(F7).
2. Right-click the target and click Download (F8).
3. Right-click the target and click Run (F9).
4. Right-click the target and click Go Online (CTRL+F11).
The Controller’s ST block appears in the ST editor as read-only and with a grey
background. In the ST editor, you can monitor the values of a variable, by
clicking the variable. You can also change and/or force BOOL variable states.
54
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Function Block Diagram Editor
FUNCTION BLOCK DIAGRAM EDITOR
Function Block Diagram (FBD) logic is one of four languages specified by the
IEC 61131-3 standard. The FBD editor is a graphical, free-form editor for editing
FBD logic in the Machine Edition environment. With the FBD editor you can work
on a disk copy of a function block diagram (offline) or monitor the execution of an
FBD running in the Controller (online). You cannot edit an FBD online.
Function Block Diagram
A Logic Developer - PC FBD is a named section of Function Block Diagram logic
that is compiled and downloaded to the PC represented by the parent target.
The graphical FBD language can be used where there is a flow of signals
between control blocks.
Navigator: Project tab
FBD nodes
FBDs can be executed as Actions called from SFC Steps or called from other
FBDs, ladder programs, or ST blocks. An FBD can contain instructions, wires,
and variables, as well as ladder user-defined function blocks (UDFBs), and ST
UDFBs.
Want to know more? In the Help Index, look up “FBD: an Overview (PC)”.
T o ope n an F BD f o r edi ti n g
• In the
Project tab of the Navigator, under the
Logic folder, or under a
user-defined folder, double-click an
FBD node.
Your FBD opens in the FBD editor.
To crea te a ne w FBD
1. In the
Project tab of the Navigator, right-click the
Logic folder or a
userdefined folder, point to New, and click Function Block Diagram.
A new, empty
FBD with the default name “FBDBlkn” appears in the Navigator
in alphabetical order under its folder.
2. (Optional.) Enter a unique name for the FBD.
Your new FBD appears under the Logic folder or under a user-defined folder.
GFK-1868Q
Proficy* Machine Edition* 7.50
55
3
Logic Developer - PC
Function Block Diagram Editor
Working with the FBD editor - Offline
The FBD editor interacts with the Machine Edition tools to provide maximum
flexibility when editing a program. The following picture illustrates some of the
operations you can perform.
Drag variables
to the FBD editor to complete
FBD instructions.
Drag instructions from the
PC FBD
Instructions
drawer of the
Toolchest.
Locate all
instances of a
variable in the
References
tab of the
Feedback
Zone.
The Companion automatically provides
information on
what you click.
To ins ert a n FB D te xt box ( Toolches t me thod)
1. If you have not already done so, open the
2. In the Toolchest, choose the
3. Expand the
Toolchest.
PC FBD Instructions drawer.
Comment Block folder.
4. Drag the text box from the Toolchest onto a blank area of the FBD editor.
You can now enter text in the FBD editor.
56
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Function Block Diagram Editor
To ins ert a n FBD t ext box ( FBD e ditor me thod)
1. In the FBD editor, right-click a blank area and click Insert Instruction.
2. In the smart list that appears, do one of the following:
Enter the word “text” (without quotes), and then press ENTER.
- or Scroll down the list, choose Text, and then press ENTER.
3. You can now enter text in the FBD text box.
To ins ert a n FBD inst ruct ion ( Toolc hest met hod)
1. If you have not already done so, open the
Toolchest.
2. In the Toolchest, choose the PC FBD Instructions drawer
3. Expand an FBD instruction group.
4. Drag an
FBD instruction from the Toolchest onto a blank area of the FBD
editor.
5. Assign parameters above (for Call, Counter, and Timer
instructions) and beside the FBD instruction, or draw wires
to or from the FBD instruction.
To ins ert a n FBD inst ruct ion ( FBD edit or met hod)
1. In the FBD editor, right-click a blank area and click Insert Instruction.
2. In the smart list that appears, enter or choose an
FBD instruction.
3. Assign parameters above (for Call, Counter, and Timer instructions) and beside
the FBD instruction, or draw wires to or from the FBD instruction.
GFK-1868Q
Proficy* Machine Edition* 7.50
57
3
Logic Developer - PC
Function Block Diagram Editor
Working with the FBD editor - Online
In the FBD editor, you can view the execution of an FBD as it runs. This is
illustrated in the following diagram.
The grey
background
indicates that
the editor is
online to the
Controller and
is read-only.
Online status
is indicated by
the color of
the target
icon.
Right-click any
BOOL variable
to force it
On/Off or to
turn it On/Off.
Use the Data Watch tool to
view or set data values for
any variable in your project.
Online FBD editing is not supported. However, you can change or force BOOL
variable states. While online, you can also watch data variables in the Data
Watch tool.
To watc h a varia ble ’s value
• In the FBD editor, right-click a variable whose value you want to monitor and
click Watch.
The variable is added to the
58
Proficy* Machine Edition* 7.50
Data Watch tool for monitoring.
GFK-1868Q
Logic Developer - PC
Logic Developer - PC Web Access
LOGIC DEVELOPER - PC WEB
ACCESS
Machine Edition enables you to view a target’s PC logic data with a web
browser, such as Microsoft Internet Explorer (version 4.0 or later is required).
When a Machine Edition project is downloaded, it automatically launches an
integrated web server. Users who connect to the target computer over the web
are presented with the Site Index, from which they can select the Logic
Navigator. (If the target has an HMI, Web Access options for the HMI appear as
well.)
The Logic Navigator presents a tree diagram of PC logic stored in the Controller,
where you can browse to specific programs and blocks:
■
Published SFCs and SFC macros.
■
Ladder program.
■
Ladder subroutines.
■
Actions.
■
ST blocks.
■
IL blocks
Click any logic block in the tree to view it.
Want to know more? In the InfoView tab of the Navigator, expand the Web Access library,
and then select a topic under the “PC Web Access features” book.
To al low r emot e ac cess to your proj ec t
1. For each target that you want to allow access to, set the
target’s Publish Logic
property to True.
This enables all PC logic except SFCs and SFC macros to be remotely
viewable.
2. For each SFC and SFC macro in those targets that you want users to access,
set its Publish property to True.
For example, to allow users to view an SFC remotely, set the SFC’s Publish
property to True.
NOTE
GFK-1868Q
The target containing the PC logic to be published must be set as the active target and
a successful project download must occur.
Proficy* Machine Edition* 7.50
59
3
Logic Developer - PC
Logic Developer - PC Web Access
To acce ss t he PC logi c S i te I nde x
1. Start Internet Explorer.
2. In the Address box in Internet Explorer, enter the computer name or IP address
of the run-time computer.
3. If you are not sure what the run-time computer’s name or IP address is, check
the properties of the TCP/IP driver in the Control Panel Network setup, or
contact your network administrator.
4. If you are testing the project on the local computer, enter “localhost” (without the
quotation marks) as the Address. This connects Internet Explorer with the local
computer.
When you connect to the run-time computer, the Site Index appears with a list of
links to possible ways to view your process data.
T o vi ew P C l o gi c r emot el y
1. Start Internet Explorer.
2. In the Address box in Internet Explorer, enter the computer name or IP address
of the run-time computer.
The Site Index appears.
3. Click Logic, and then click Logic Navigator.
An index (tree diagram) appears, which contains all published PC logic.
60
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Logic Developer - PC Web Access
4. Click the SFC, SFC macro, ladder program, ST block, or IL block you want to
view.
The selected PC logic block appears. See To allow remote access to your
project above for information on publishing PC logic.
While viewing ladder logic remotely, you can view the values of variables by
hovering the mouse pointer over the variable. The value of a BOOL variable on a
Coil or Contact instruction is identified by its color:
■
If it is green, the variable is set to True (1).
■
If it is black, the variable is set to False (0).
You can view the values of variables in SFC Transitions (including Structured
Text Transition statements) by hovering the mouse pointer over the Transition.
The color of an SFC Transition indicates its result:
Click to go back
to the Logic
Developer - PC
main menu.
■
If it is green, its result is True (1).
■
If it is black, its result is False (0).
Click an SFC
action to view
it remotely.
Hover over an
SFC transition
with the mouse
pointer to view its
value or values.
GFK-1868Q
Proficy* Machine Edition* 7.50
61
3
Logic Developer - PC
Control I/O Drivers
CONTROL I/O DRIVERS
A control program (SFC, ladder, IL, ST, or FBD) generally interfaces with the
process it is controlling through some type of physical I/O equipment. For PCbased control systems this usually involves installing an adapter card in the
target computer that connects to an industry standard I/O network. In this way,
data generated by a process can be acquired and acted upon by the Controller
as it executes its program(s). Control I/O drivers provide the software required to
connect the Controller with an adapter card and the I/O network of your choice.
Want to know more? In the Help Index, look up “Control I/O Drivers”.
I/O Drivers
Logic Developer - PC comes complete with a growing library of drivers. Drivers
that require no additional equipment on the target computer are the following:
■
ASCII: Enables you to use an existing communications port on the target
computer to send and receive ASCII formatted data to and from other
equipment.
■
Control Peer: Enables Controllers running on two or more computers to
share process data. Messages are passed via ethernet when variable values
change.
Navigator: Project tab
Control I/O nodes
Other drivers require third-party adapters on the target computer. Logic
Developer - PC supports most of today’s most popular I/O networks including
the following:
■
Allen-Bradley RIO
■
Honeywell SDS I/O
■
ASCIIa
■
Interbus-S I/O
■
Control Peer Driver
■
Modbus Slave1a
■
DeviceNet I/Oa
■
Modicon MB + Distributed I/O
■
Modicon Quantum-800 Series I/O
Driver
I/Oa
■
Ethernet
■
Fanuc CNC I/O
■
PROFIBUS I/Oa
■
GE Series 90-30 I/Oa
■
VersaMax Expansion I/Oa
■
GE Genius I/O2
a. Also supported on QuickPanel Control targets
62
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Control I/O Drivers
To add a Contr ol I/O driver t o a ta rget
• Right-click the
Control I/O Drivers node, point to New Driver, and choose a
driver from the list.
The new driver appears as a
child node under the
Control I/O node. A
default configuration of the driver is also added to the Control I/O tool. You can
add up to nine drivers to a target.
Control I/O Tool
Control I/O
The Control I/O tool is a special editor used to graphically model the I/O
equipment driven by Control I/O drivers. Each I/O system is displayed in a tree
structure starting with a
driver node branching down to terminals that
represent physical field connections. Between the driver and terminals are
nodes representing any
cards,
racks, or modules included in the
system. Field data is shared with the components of your project by mapping
variables to each I/O terminal.
Want to know more? In the Help Index, look up “Control I/O Tool”.
GFK-1868Q
Proficy* Machine Edition* 7.50
63
3
Logic Developer - PC
Control I/O Drivers
Working with Control I/O
The Control I/O tool interacts with other Machine Edition tools to speed the
creation of your I/O system. The following picture illustrates some of the
operations you can perform.
IEC addresses
can be displayed in a ladder program
above variables mapped
to I/O terminals.
Drag variables
from the ladder editor to
Control I/O terminals.
Use the Variable List to create variables
then drag them
to I/O terminals.
Double-click a
node to configure a driver,
card, rack, or
slot.
Double-click a
terminal and
type a name to
create and
map a variable
of the default
type.
View and edit
data values for
variables
mapped to I/O
terminals.
To configure a n I/O sy ste m with t he Contr ol I/O tool
1. Right-click a
driver,
card,
rack, or
slot and click Add xyz to build an
I/O tree.
2. Double-click a driver, card, rack, or slot node to configure it.
3. Map variables to
64
Proficy* Machine Edition* 7.50
I/O terminals.
GFK-1868Q
Logic Developer - PC
Controller
CONTROLLER
The Controller is a run-time engine, hosted on a
following operations in a repeated scan cycle:
■
■
■
■
■
■
target, that performs the
Solves logic in a ladder program, including any called subroutines.
Solves logic in an SFC, including any called actions.
Solves ST block named ‘MAIN’ (if it exists), including any called subroutines.
Solves FBD block named ‘MAIN’ (if it exists), including any called
subroutines.
Interfaces with Control I/O drivers.
Updates the target’s run-time database, which is shared with the View
Runtime (see page 93).
The following diagram illustrates the Controller’s scan cycle.
Read from I/O
Solve ladder
Navigator: Project tab
Solve SFC
Target node
Yield
Solve ST Block
Write to I/O
Solve FBD Block
Logic Developer - PC Run-time Controller Scan Cycle
The Controller can be hosted on a:
■
Windows PC target. The Controller appears as a Logic Developer - PC
system service.
■
QuickPanel View/Control target. The Windows QuickPanel Control appears
as a Logic Developer - PC Controller program.
You specify a target when creating a project. The Controller automatically starts
when the target operating system is started.
Want to know more? In the Help Index, look up “PC Logic Controller: an Overview”.
GFK-1868Q
Proficy* Machine Edition* 7.50
65
3
Logic Developer - PC
Controller
Working with the Controller
The Controller’s location (IP address or computer name), performance (scan
rate or tuning), and behavior (response to faults, watchdog timer, and shutdown
procedure) are configured by setting the properties of the target it resides on.
To configure t he Cont rolle r
1. In the
Project tab of the Navigator, right-click a
target and click Properties.
2. In the
Inspector, adjust the properties.
If your project includes an HMI component, properties of the View Runtime can
also be set at this time. You can also configure the Controller’s properties by
selecting Properties from the Controller menu. In this case, the Controller
Properties dialog box appears. The information in the dialog box is the same as
in the Inspector—just represented differently.
The logic component of a project must be downloaded to the Controller before
the project can be run.
To dow nloa d a logic c omponent t o the C ontroller
• In the
Project tab of the Navigator, right-click a target and click Download.
All components on the selected target are validated and, if no errors exist, they
are downloaded to the specified computer. Errors listed in the Build tab of the
Feedback Zone must be corrected before a download can be completed. Logic
components are downloaded to the Controller, while HMI components are
downloaded to the View Runtime.
Although the Controller service is always running, you still have control over the
execution of your control programs. Offline, you can start, stop, and reset
execution. When online to the Controller, additional commands are available to
pause, single-scan, or enable forces.
Run Mode St ore
With the Run Mode Store (RMS) functionality, you can update a target
Controller’s program without stopping the Controller. It is supported on all Logic
Developer - PC targets.
When you attempt to download your project to the Controller, the Download to
Controller dialog box appears with the following options.
■
66
Proficy* Machine Edition* 7.50
Attempt a Run Mode Store: Machine Edition attempts a Run Mode Store
operation. That is, it tries to download your logic to the Controller while the
Controller is running.
GFK-1868Q
Logic Developer - PC
Controller
■
Stop the Controller, then download: Machine Edition does not attempt to
use the Run Mode Store feature. Instead, it stops the Controller before
initiating the download operation.
■
Download Retentive Initial Values: Choose whether to download initial
values of retentive variables, which may have changed since the previous
download.
Several system tests and checks are performed when attempting a Run Mode
Store operation. If these tests fail, the logic program may not be downloaded to
the Controller.
Want to know more? In the Help Index, look up “Run Mode Store (RMS) (PC)”.
To run t he Cont roller
• In the
Project tab of the Navigator, right-click a target, point to Online
Commands or Offline Commands, and click Start Runtime.
The ladder program, SFC program(s), the ST block named ‘MAIN’, and the FBD
block named ‘MAIN’ begin executing on the target computer or unit. If the target
also has an HMI component (see page 93), the View Runtime is started at the
same time as the Controller.
To validate, download and run a project, right-click a
Download and Start “targetname”.
target and click
Warm Standby
The Warm Standby feature provides an extra level of reliability for critical
Windows PC and QuickPanel Control applications. It consists of two Controllers
running the Logic Developer - PC Controller (a primary and secondary or warm
standby Controller), and an I/O switch that determines which Controller is
currently connected to the physical I/O.
When a system using warm standby is started, the primary Controller is
connected to the I/O, solves logic, and updates the secondary Controller with
critical data. The secondary Controller receives the data and monitors the status
of the primary Controller. When a fault is detected in the primary Controller, or
when the secondary Controller cannot communicate with the primary Controller,
the I/O connection is automatically switched to the secondary Controller and the
secondary Controller takes over operations.
GFK-1868Q
Proficy* Machine Edition* 7.50
67
3
Logic Developer - PC
Controller
Working with Warm Standby
You must set up the warm standby hardware before you can configure the warm
standby system.
Want to know more? In the Help Index, look up “warm” and choose “Warm Standby”.
To configure Wa rm Sta ndby
1. In the
Project tab of the Navigator, right-click a
Control target and click Properties.
Windows PC or QuickPanel
2. In the
Inspector, scroll to the +Redundant System group of properties and
double-click it to expand the group.
3. Click the Redundant Mode property and click Warm Standby.
4. Click the Controller Mode property and choose a value from the list.
Hot Standby
The Hot Standby feature provides a high level of reliability for critical Windows
PC applications. It consists of two Controllers running the Logic Developer - PC
Controller (a primary and secondary or hot standby Controller) over a GE
Genius I/O network. The GE Genius driver automatically handles the switching
between the Controllers.
To download to a target with hot standby, the primary and secondary Controllers
must be synchronized, that is, they must both be downloaded.
By default, the primary Controller is active and the secondary Controller is the
backup. The backup Controller sets itself to active when one of the following
takes place:
■
A fault of a specified type occurs. (See To configure a Hot Standy, below.)
■
A loss of communication occurs with the active Controller via the VMIPCI5565 reflective memory cards.
■
The target's Secondary Switch Time has elapsed.
Both Controllers can read from the network; however, only the active Controller
can write to the network.
Working with Hot Standby
You must set up the hot standby hardware before you can configure the hot
standby system.
Want to know more? In the Help Index, look up “hot” and choose “Hot Standby”.
68
Proficy* Machine Edition* 7.50
GFK-1868Q
Logic Developer - PC
Controller
To configure H ot Standby
1. In the
Project tab of the Navigator, right-click a
click Properties.
Windows PC target and
2. In the
Inspector, scroll to the +Redundant System group of properties and
double-click it to expand the group.
3. Click the Redundant Mode property and click Hot Standby.
4. Click the Secondary Address property and enter the IP address (Controller
name) of the secondary Controller.
5. Click the Secondary Switch Fault property and choose the type of fault the
secondary Controller will become active on.
6. Click the Secondary Node ID property and assign a unique node ID to the
VMIPCI-5565 card of the secondary Controller.
7. Click the Secondary Switch Time (ms) property and enter the number of
milliseconds the secondary Controller is to wait for communication from the
primary Controller before setting itself up as the active Controller.
8. Click the Primary Node ID property and assign a unique node ID to the VMIPCI-
5565 card of the primary Controller.
9. Click the Primary Wait Time (ms) property and enter the number of milliseconds
the primary Controller is to wait for communication from the secondary Controller
before setting its synchronization bit to False.
OPC Servers, Warm Standby, and Hot Standby
Warm standby and hot standby are fully supported by the Logic Developer - PC
OPC server for Machine Edition. When a configuration file is detected, the OPC
server does the following:
■
It generates internal objects so that it recognizes all warm standby or hot
standby configurations as logical Controllers to OPC clients.
■
It creates predefined OPC items for each logical Controller. These items
indicate which physical Controller is active and the statuses of the primary
and secondary Controllers.
To configure a n O PC s erv er for H ot Standby a nd Warm St andby
• Edit the “OPCWarmStandby.HTML” file, located in the same folder as
LogicPC_OPC.EXE on the computer hosting the OPC Server.
This XML file is used for both the Warm Standby and Hot Standby features. By
default, this file is located in the
“C:\Program Files\Proficy\Proficy Machine Edition\OPC” directory.
GFK-1868Q
Proficy* Machine Edition* 7.50
69
3
70
Logic Developer - PC
Controller
Proficy* Machine Edition* 7.50
GFK-1868Q
4
View*
View is the human-machine interface (HMI) component of Machine Edition,
providing the means to organize, track, display, and affect data from your plant
or process. With View you create graphical panels, write scripts, configure alarm
and logging schemes, and launch the project in View Runtime. View supports
HMI creation for Windows 7 and Windows XP (“Windows PC” targets for short),
QuickPanel View/Control* targets (“QPV/C” targets for short), and QuickPanel
targets.
For Windows PC and QPV/C targets, Web Access features publish data from
Machine Edition HMIs for remote viewing over the Internet. Most View tools and
editors are common to all targets, but a few are QuickPanel-specific; for details,
see “QuickPanel Applications” on page 95.
The following are included with a View HMI component:
Navigator: Project tab
HMI component nodes
■
■
■
■
■
■
■
■
■
■
■
■
Panel Editor
Script Editor
Alarms
PLC Access Drivers
Language translation support
Message groups
Logging (Windows PC and QPV/C targets only)
OPC Client & Servers (Windows PC and QPV/C targets only)
Web Documents (Windows PC and QPV/C targets only)
Data Logging Windows (Windows PC targets only)
View Runtime (Windows PC and QPV/C targets only)
Password security (QuickPanel targets only)
To crea te a pr oje ct t hat include s an HMI c omponent
1. In the
Manager tab of the Navigator, right-click
My Computer and click
New.
2. In the New Project dialog box that appears: in the Project Name box, enter a
name for your project.
3. From the Project Template list, choose “Configuration Wizard (View /
Control)”.
GFK-1868Q
Proficy* Machine Edition* 7.50 71
4
View*
Panel Editor
4. In the preview pane, select the desired parameters for your new application
(such as the target type and model).
5. Click OK.
Your new project is created and the Project tab opens in the Navigator.
PANEL EDITOR
The Panel Editor is used to develop the layout of each panel in your HMI
application. Each panel is a single screen or window of the HMI. You draw and
configure graphical objects on the panel to create each screen.
Graphical objects are the various graphical elements of the HMI screen, such as
rectangles, polygons, buttons, alarm displays, real-time graphs, and historical
trend graphs. All objects are available from the Drawing Tools toolbar. Many
items perform actions when you tap them at run time.
The Panel Editor displays the current panel as it will appear on the target unit’s
screen. In addition, the Panel Editor adds a drawing grid of dots to assist you in
lining up a series of graphical objects with each other.
■
■
Navigator: Project tab
Panel Nodes
On Windows PC and QuickPanel View/Control targets, many graphical
objects can be configured with several types of Animation to move, change
color, display data, trigger scripts, and receive input during Runtime.
On QuickPanel targets, the Panel Editor also has a tiling grid. The tiles let you
align graphical objects with the touch-sensitive cells on the surface of a
QuickPanel unit’s display.
Want to know more? In the Help Index, look up “panels” and choose “Graphical Panels”.
To add a new panel t o a n H MI
• In the
Project tab of the Navigator, right-click the
Graphical Panels folder
and click New Panel.
A new panel is added beneath the Graphical Panels folder in the Navigator. If
you have created a project by using a template, the Graphical Panels folder
likely already contains some default panels.
To ope n a panel for e dit ing
• In the
Project tab of the Navigator, double-click a
The panel appears in the Panel Editor.
72
Proficy* Machine Edition* 7.50
panel node.
GFK-1868Q
View*
Panel Editor
To configure a pa nel
1. In the
Project tab of the Navigator, right-click a
The Inspector displays the panel’s properties.
panel and click Properties.
2. Set the panel’s properties in the Inspector.
For a description of the panel properties, select a property and look in the
Companion. Click
in the Tools toolbar to open the Companion window if it is
not already open.
Working with the Panel Editor
The Panel Editor interacts with all of the Machine Edition tools to assist you in
the construction of graphical panels. The following picture illustrates some of the
operations you can perform.
Want to know more? In the Help Index, look up “panels” and choose “Working with Panels”.
View toolbars provide drawing and
object manipulation tools.
Existing graphical objects can
be resized and
edited directly in
the Panel Editor
Panels are listed
in the Project tab
of the Navigator.
Drag items from
the View Expert
Objects drawer of
the Toolchest to
the Panel Editor.
Configure graphical objects in the
Inspector.
The Feedback
Zone updates
with information
when you validate, download,
or run your project.
The Companion
displays information for the currently selected
object, tool, or
property.
To dr aw a gra phic al obje ct
1. If the Drawing toolbar is open, select the tool you want to use. Otherwise, right-
click in the Panel Editor and choose a drawing tool.
The Companion displays instructions on how to use the selected tool.
2. Follow the instructions in the Companion to draw your object.
After drawing the object, set its properties in the Inspector.
GFK-1868Q
Proficy* Machine Edition* 7.50 73
4
View*
Panel Editor
To ani mat e an obj ect (Windows PC and Quick Pa nel Vi ew /C ontrol ta rget s only)
• In the Panel Editor, double-click a graphical object.
The Animation Properties dialog box appears. Settings for each type of
animation are grouped on its own tab. Animations become active when the
project is launched with View Runtime.
Message Displays
The
Local Message Display,
Triggered Message Display, and
Local
Image Display graphical objects display different messages or images based on
the values or states of associated variables. Each of these three objects is
associated with a message group of an appropriate type under the
Message
Groups folder—an
IMD Group,
TMD Group, or
IID Group.
Each graphical object can be associated with only a single message group, but
that message group may be associated with many graphical objects. (On
QuickPanel targets, the size of all graphical objects associated with the same
message group must be the same; this size is set in properties of that message
group.) You can open the grid for an associated message group by clicking the
button in the object’s “IMD/TMD/IID Group” property.
Entries in a message group are edited in an appropriate grid editor.
■
Navigator: Project tab
Message Group Nodes
An
Indexed Message Display graphical object shows text messages that
change depending on the value or state of a single associated variable. The
colors and appearance of the display can also change. The values and
related appearances are set by the display’s associated
IMD Group.
Want to know more? In the Help Index, look up “IMD” and choose “IMD (Local Message
Display) group” and “IMD (Local Message Display) grid”.
■
A
Triggered Message Display graphical object shows text messages that
change depending on the results of boolean expressions. The colors and
appearance of the display can also change. The values and related
appearances are set by the display’s associated
TMD Group.
Unlike a Local Message Display, you do not associate a variable with a
Triggered Message Display. Instead, you specify a series of boolean
expressions in the TMD Group grid editor.
Want to know more? In the Help Index, look up “TMD” and choose “TMD (Triggered
Message Display) group”, “TMD (Triggered Message Display) grid”,
and “Trigger Expression dialog box (TMD grids)”.
■
74
Proficy* Machine Edition* 7.50
An
Indexed Image Display shows different images depending on the
value or state of a single associated variable. The values and related images
are set by the display’s associated
IID Group. An image in an IID Group is
GFK-1868Q
View*
Script Editor
typically a bitmap, imported from a BMP file. Images can also be sets of
simple graphical objects (Arcs, Bitmaps, Circles, Lines, Pie Wedges,
Polygons, Polylines, Rectangles, Round Rectangles, and Text).
Want to know more? In the Help Index, look up IID and choose “IID (Local Image Display)
group” and “IID (Local Image Display) grid”.
SCRIPT EDITOR
The Script Editor is a text editor for the various HMI scripting languages, such as
ViewScript, VBScript, and QPScript. On Windows PC targets, you can also use
Structured Query Language (SQL) commands to access a database for which
an Open Database Connectivity (ODBC) driver is installed.
Scripts
Navigator: Project tab
Script nodes
Scripts are short executable programs composed of a sequence of instructions
that tell a project, panel, or touch-animated object how to react to events during
run-time. There are four types of scripts:
■
Application Scripts: An application script is associated with an entire target
and can be configured to execute when you start or quit the application (in
View Run-time) or based on a frequency or condition while the application
runs.
■
Panel Scripts: A panel script is associated with a specific panel in a target
and can be configured to execute when the panel opens, when the panel
closes, or based on a frequency or condition while the panel is open.
■
Touch Animation Scripts: (Windows PC and QuickPanel View/Control
targets only.) At run time, Touch Animation scripts are activated with
keystrokes and on-screen buttons. They are written directly in configuration
dialog boxes of graphical objects.
■
Global Function Library Scripts: (Windows PC targets only.) Global
Function scripts are associated with an entire target. By default, they are
executed before any other scripts, but they can be configured to run
periodically or on a condition. They must be written in an Active Scripting
language, like VBScript.
To crea te, open, and edit a n applic ation sc ript
1. In the
Project tab of the Navigator, right-click the
Application Scripts node,
point to New Script, and click either VBScript or ViewScript. (For more
information on scripting, see page 76.)
2. Enter a name for the new application script.
GFK-1868Q
Proficy* Machine Edition* 7.50 75
4
View*
Script Editor
A new script is added to the Application Scripts node.
3. Double-click the
script to open it in the Script Editor and begin editing the
script.
4. In the Inspector, edit the application script properties.
To crea te, open, and edit a panel scr ipt
1. In the
Project tab of the Navigator, right-click a
panel node, point to New
Script, and choose either VBScript or ViewScript. (For more information on
scripting, see page 76.)
2. Type a name for the new panel script and press ENTER.
A new script is added to the panel node.
3. Double-click the
script to open it in the Script Editor and begin editing the
script.
4. In the Inspector, edit the panel script properties.
To crea te a t ouch anima tion scr ipt
1. In the Panel Editor, double-click the object you want to animate. The Configure
Animation dialog box appears.
2. Click the Touch tab.
3. Select the Enable Touch Action Animation check box and choose a touch action
command that will execute a script.
4. In the large edit box, type the script that will run when the object is touched.
To crea te a global f unc ti on libr ary s cript
1. In the
Project tab of the Navigator, right-click Global Functions, point to
New Library, and click VBScript.
A new script is added to the Global Functions node.
2. Double-click the script to open it in the Script Editor and begin editing the script.
3. In the Inspector, edit the Global Function Library script properties, in other
words, the name.
Scripting Languages
On Windows PC and some QuickPanel View/Control targets, Machine Edition
supports two types of scripting languages: the proprietary ViewScript language
and VBScript Active Scripting languages (using Microsoft’s Active Scripting
engine). On other QuickPanel View/Control targets, Machine Edition supports
only proprietary ViewScript language.
On QuickPanel targets, Machine Edition uses the proprietary QPScript language
(see page 96).
76
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
Script Editor
ViewScript scripting language
The ViewScript scripting language consists of the following:
■
Keywords: View script keywords are a basic set of commands that are used
to control the flow of a script and to create local variables.
■
Operators: View operators are used to assign variable values and to perform
mathematical operations
■
Script Functions: View script functions are commands that can be written into
the body of your script to monitor and react to changes in variable values.
Functions are grouped in the following categories: ActiveX, Alarm
Management, Animation, Application Access, CSV, File Management,
Initialization File Management, List and Combo Box, Logging, Miscellaneous,
Network, Panel Management, Screen Navigation, Security, Serial
Communication, Statistical Process Control, SQL, String, System, Trend
Management, Video/Sound, and Web.
■
Comments: Placing comments in, or between, the lines of your script is useful
for debugging your script and for future reference.
Want to know more? In the Help Index, look up “Viewscript” and choose “ViewScript HMI
scripting language”.
Active Scripting
Active Scripting lets Machine Edition use external scripting languages through a
COM interface. Active Scripting languages are supported only on Windows PC
and some QuickPanel View/Control targets. Currently, only the VBScript Active
Scripting language is supported.
By default, new projects use VBScript. You can override this default by setting a
user preference.
A target can contain scripts written in either ViewScript or VBScript. Because
troubleshooting such a project can be quite difficult, this practice is not
recommended.
Want to know more? In the Help Index, look up “scripts” and choose “View Scripts: an
Overview”, or look up “scripting” and choose “Active Scripting in View:
an Overview”.
Va lida ti ng a scr ipt writt en in an Act i ve Script ing language
Active scripting languages are validated at run-time. You can also validate a
project at any time during development to check:
GFK-1868Q
■
Syntax for View function calls.
■
Syntax for variable, array, and structure element references.
Proficy* Machine Edition* 7.50 77
4
View*
Script Editor
■
Limited checks for VBScript syntax.
VBScript Syntax
A detailed explanation of VBScript syntax is beyond the scope of this manual.
For more information on the VBScript language usage, syntax and examples,
look up VBScript at Microsoft’s website (www.microsoft.com).
Want to know more? In the Help Index, look up “VBScript” and choose “VBScript language:
an Overview”.
Active Scripting Objects
Active Scripting provides a mechanism to extend a scripting language through
custom COM objects. Variable syntax is, therefore, limited to using properties
and methods on a COM object.
There are four types of objects in VBScript:
■
Variable objects.
■
Array objects.
■
Structure objects.
■
Application objects.
Want to know more? In the Help Index, look up “VBScript” and choose “VBScript language:
an Overview”.
Working with the Script Editor
The Script Editor interacts with other Machine Edition tools to provide maximum
flexibility when editing a script. The following picture illustrates some of the
operations you can perform.
Want to know more? In the Help Index, look up “editor” and choose “Working in the View
Script Editor”.
There are many ways to insert script words when writing scripts.
■
If you are very familiar with the operators, functions, and keywords used in
the Script Editor, start typing your script directly in the Script Editor.
■
Otherwise, right-click where you want to insert a function, operator, or
keyword and click Insert. Then point to the appropriate submenu for the item
you want to insert and select it from the list that appears. Submenus are also
available for names of the project’s variables, panels, scripts, alarm groups
and logging groups. For a description of a script function, keyword, or math
78
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
Grid Editors
A script can be
set to activate
periodically or
on a condition.
The View Scripting drawer of the
Toolchest contains script functions, keywords,
and math operators that you can
drag into your
scripts.
Application
scripts are displayed under
the Application
Scripts folder.
Panel Scripts
are displayed
under the panels to which
they belong.
The Companion
displays help for
the currently
selected script
function, keyword, math operator, or property.
operator, while in the Script Editor, move the cursor on the word and press
F1.
■
All the math operators, script functions, and script keywords are also listed in
the Toolchest and can be dragged into your script. The Companion provides
a description of each item.
GRID EDITORS
With various grid editors, you can create and edit several items in your HMI
targets within a spreadsheet-like table. Among the features that use grid editors
are:
GFK-1868Q
■
Word Alarm groups
■
Bit Alarm groups
■
IMD (Local Message Display) groups
■
TMD (Triggered Message Display) groups
■
Selector Switches
■
Bar Graphs
■
Language translations
Proficy* Machine Edition* 7.50 79
4
View*
Alarms
■
■
■
Trend displays
Passwords list (QuickPanel targets only)
External Keypad assignment configuration
The exact functionality depends on the specific editor, but in general you can:
■
Double-click a cell to edit its contents.
■
Right-click a cell to perform various operations on the cell.
■
Select an entire row (by clicking the grey button row headers on the left), then
right-clicking the selection to perform operations on the row
Want to know more? In the Help Index, look up “Working with QuickPanel grid editors”.
You can also press F1 while working in the grid for a description of
that editor.
ALARMS
Alarms are messages that appear on a display in response to specified
conditions in the system. These messages typically inform the operator of a
situation that requires immediate attention. When a variable satisfies one of its
alarm conditions, it goes into an alarm state.
The alarm system for a HMI application consists of several different elements.
Alarm Groups
There are three general types of alarms, organized into three subfolders under
the
Alarm Groups folder:
■
Word Alarm Groups and
Bit Alarm Groups are tables of variables,
variable values, and associated alarm messages. When the value of a
variable matches an entry in one of these tables, it goes into an alarm state
and the appropriate message is added to any Alarm Display objects on the
target.
■
Variable Alarms (Windows PC and QuickPanel View/Control targets
only) are sets of variables for which alarm limits have been configured. Unlike
Bit or Word Alarms, you assign a variable to an alarm group in properties of
the variable itself. Variable alarm groups help you organize related alarmed
variables. Also, using more than one variable alarm group makes it easier to
manipulate and view alarm data at run time. A history of alarm group data can
be logged daily for future analysis. You can also configure e-mail notification if
any of a variable alarm group’s variables go into an alarm state.
Navigator: Project tab
Alarm nodes
80
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
Alarms
Alarm Display Objects
Active alarms can be displayed at run time with Alarm Display objects. At run
time, Alarm Displays dynamically update with information about alarm states.
■
If you use variable alarm groups (Windows PC and QuickPanel View/Control
targets only), you can associate an Alarm Display with a specific variable
alarm group. Only variable alarms for alarms for variables in that group and
its subgroups will appear on that Alarm Display.
■
If you use Bit or Word alarms, alarm states and messages are based on
specific values. When a variable and its value match an entry in one of the
target’s alarm groups, the corresponding message appears in the Alarm
Window.
Want to know more? In the Help Index, look up either “Alarms (Windows PC and
QuickPanel View/Control): an Overview” or “Alarms (QuickPanel): an
Overview”.
To set a n alarm c ondit i on for Variable A la rms (Windows PC and QuickPa ne l
Vi e w/C ontrolt arge ts only)
1. In the
Variables tab of the Navigator, right-click the variable for which you
want to set an alarm condition and click Properties.
The Inspector displays the variable’s properties.
2. In the Inspector, double-click the Alarming property to set the general alarm
parameters (the priority of the alarm, its alarm group, and how long to keep a
history of alarm events).
3. Double-click the specific type of alarm (discrete alarms, limit alarms, deviation
alarms, and so on) that you want to configure to set its alarm parameters.
These parameters establish the ranges that place the variable in an alarm state.
To add a Va riable Al ar m Group
• In the
Project tab of the Navigator, under the target’s
Alarm Groups folder,
right-click the
alarm group to which you want to add the new group and click
New. Enter a name for the new alarm group.
Your new alarm group appears beneath the alarm groups node. You can now
select this new alarm group when configuring properties of the target’s variables.
To add a Bi t or Word A la rm group
1. In the
Project tab of the Navigator, under the target’s
Alarm Groups folder,
right-click the
Bit Alarms or
Word Alarms folder (as appropriate) and click
New.
2. Enter a name for the new alarm group.
GFK-1868Q
Proficy* Machine Edition* 7.50 81
4
View*
Logging data
Names must be unique within a target. You can double-click the Alarm Group to
edit it.
To crea te a n A l arm D is pl ay gra phi c al obj e ct
1. In the Panel Editor, right-click and click Alarm.
The
Alarm tool is selected.
2. Draw an Alarm Object, using the information in the
Companion as a guide.
3. Right-click the Alarm Object and click Properties.
The Inspector displays the object’s properties.
4. In the Inspector, edit the alarm object’s properties as desired.
The Alarm Display objects supported by Windows PC and QuickPanel
View/Control are not the same as those supported by QuickPanel targets. The
objects, though similar, have distinct functionalities. For help on a specific
property, click the property when the Companion window is open.
LOGGING DATA
(Windows PC and QuickPanel View/Control targets only.)
Logging keeps a history of data changes in your project for later analysis.
Logging groups help sort and organize your project data. By default, all data is
logged using the same logging strategy. If you want variables to have different
logging strategies, you can create a hierarchy of logging groups.
Logging Strategies define when data is logged for a group of variables. You can
configure a group to log data periodically, on data changes, or on a condition.
For example, one logging group might log data every minute, whereas another
might log data every five minutes.
Navigator: Project tab
If you are using a Proficy Historian 2.0 (or later) system, you can specify that
logging of data from a View HMI be sent to a Historian Collector. A Collector
sends data to a central Historian Server for storage and analysis. With a
Collector, logging groups have no effect.
Logging Group nodes
Want to know more? In the Help Index, look up “Logging: an Overview”, “Logging Groups:
an Overview, “View Historian Collector”, and “Data Logging Windows”.
To enable logging of a var ia ble
1. In the
Variables tab of the Navigator, right-click a variable and click
Properties.
82
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
PLC Access I/O
The Inspector displays the variable’s properties.
2. Set the Enable Logging property to True.
Logging is enabled for the variable, with RootLoggingGroup as the default
logging group.
To add a new logging group
1. In the
Project tab of the Navigator, right-click the
logging group node
where you want to add the new group, and click New.
2. Enter a name for the new logging group.
Your new logging group appears beneath the logging group node.
To view or edit the logging group properties, right-click it and click Properties.
During Runtime, the group will log variable data according to its properties. View
information about selected properties in the Companion. Click
on the Tools
toolbar to open the Companion if it is not already open.
PLC ACCESS I/O
PLC Access I/O is used to enable your Machine Edition HMI unit to
communicate with I/O devices on the run-time network. Typically, an I/O device
is a Controller: a special hardware device that controls input and output for other,
simpler devices. Different brands and types of Controllers communicate using
different protocols, requiring different drivers.
Drivers
PLC Access I/O is organized into View Native Drivers and View OPC Drivers.
The latter are supported for Windows PC and QuickPanel View/Control targets.
The View Native Drivers folder can contain the following:
Navigator: Project tab
PLC Access I/O Nodes
■
Drivers represent the drivers the target uses to communicate with
devices. Windows PC and QuickPanel View/Control targets can have many
drivers; QuickPanel targets can have only one.
■
Devices represent individual devices that a driver communicates with. All
devices that a driver communicates with are located in that driver folder. Most
drivers can have several devices. This enables you to talk to multiple
Controllers, or (on Windows PC and QuickPanel View/Control targets) to get
pieces of data from the same Controller at different rates.
The View OPC Drivers folder can contain multiple channels and devices:
GFK-1868Q
Proficy* Machine Edition* 7.50 83
4
View*
PLC Access I/O
■
Channels represent drivers that support serial communications between a
target QuickPanel View HMI and a PLC device by means of an OPC server.
Each channel can communicate with multiple devices.
■
Devices represent actual hardware that the HMI communicates with by
means of an OPC server. A device can be a Controller, I/O module, PC
Control, or serial device.
Want to know more? The IPI lists all of the supported PLC Access drivers. See “View,
Supported H/W”. For more information, in the Help Index, look up
“PLC Access Driver I/O”, “View Native Drivers”, and “View OPC
Drivers”.
To access data values from devices of a PLC Access driver, you must also
create variables with a PLC Access data source. The configuration of these
variables is unique for each kind of PLC Access driver; for more details, see the
online help.
If you want to connect to a GE IP Controller (whose application is created with
Logic Developer - PLC), you can use proxy variables to simplify configuration of
I/O variables in the HMI target. Proxy variables are located in an HMI target and
have HMI-only properties, but represent another variable on a GE IP Controller
target. A proxy variable’s I/O-related properties (such as its I/O address) are
automatically configured based on its source variable in the Controller target.
Want to know more? In the Help Index, look up “Proxy Variables: an Overview”.
To add a Vi e w na ti ve dr iv er t o a t arge t
1. In the
Project tab of the Navigator, expand the
PLC Access Drivers node.
2. Right-click the
View Native Drivers node, point to New Driver, and select a
driver.
The driver and a single device are added to your project and the Inspector
displays the driver’s properties.
3. In the Inspector, configure the driver. If applicable, click the
button in the
driver’s Configuration property and enter values in the dialog box.
To add a dev ic e to a V i ew Na ti ve dr iv er
1. In the
Project tab of the Navigator, under
PLC Access Drivers and under
View Native Drivers, right-click the driver to which you want to add a new
device and click New Device.
The device, with a unique default name, is added to your project.
2. (Optional.) Enter a different name for the device.
84
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
OPC
The Inspector displays the device’s properties. You can now edit the device's
properties in the Inspector.
To add a Vi e w O PC dr iv er to a t arge t
1. In the
Project tab of the Navigator, expand the
PLC Access Drivers node.
2. Right-click the
View OPC Drivers node, point to New Channel, and select a
driver.
The New Channel wizard appears.
3. Follow the wizard to the end, in order to configure the new channel (new driver).
After you exit the wizard, the configured driver is added to your project.
To add a dev ic e to a View OPC drive r
1. In the
Project tab of the Navigator, under
PLC Access Drivers and under
View OPC Drivers, right-click the driver to which you want to add a new
device and click New Device.
The New Device wizard appears.
2. Follow the wizard to the end, in order to configure the new device.
After you exit the wizard, the configured device is added to your project.
OPC
(Windows PC and QuickPanel View/Control targets only.)
OPC (OLE for Process Control) is an industry-standard protocol that enables
software applications to transmit I/O data to each other. The two applications
have a client and server relationship. You can think of OPC Servers as being
producers of information and OPC Clients as being consumers:
■
The OPC Server has data that it makes available to various OPC Clients.
■
The OPC Client connects to an OPC Server to gain access to the server’s
data.
Because OPC is an industry standard, any OPC Client can access data from
any OPC Server, regardless of the manufacturer. Machine Edition implements
both the client and the server side of OPC communications.
Want to know more? In the Help Index, look up “OPC: an Overview”.
Navigator: Project tab
OPC Client Nodes
GFK-1868Q
Because an OPC Server and OPC Client are simply programs or applications,
they can run on the same computer. For example, in your factory you could have
Proficy* Machine Edition* 7.50 85
4
View*
OPC
another application that supports an OPC Client and a Machine Edition
application running on the same computer. To allow them to share data, you
would set up one of them as an OPC Server and the other as an OPC Client,
then have the client application establish a connection to the server.
OPC communications rely heavily on Microsoft’s OLE and DCOM technology. If
the OPC Server and an OPC Client are running on different computers, you
must edit the DCOM Security settings on one or both computers.
Want to know more? In the Help Index, look up “DCOM” and choose “Configuring DCOM
Security for OPC Communications”.
The OPC specifications are set and maintained by the OPC Foundation, a nonprofit organization. You can find detailed technical information about OPC on the
OPC Foundation web site at www.opcfoundation.org.
OPC Client
The OPC Client driver enables your Machine Edition application to communicate
with OPC Servers. This lets Machine Edition act as a client in the OPC
Client/Server relationship. The View OPC Client driver supports all interfaces
required under the OPC 1.0a, 2.0, and 3.0 specifications.
The OPC Client folder is added to a target when you add an HMI component.
Each OPC Server that the application communicates with is located under the
OPC Client folder, much like devices of a PLC Access driver.
To access data values from an OPC Server, you must also create and configure
variables with an OPC data source.
To add an OPC Se rver l i nk t o t he OP C Cl i ent fol der
1. In the
Project tab of the Navigator, right-click the
New Server Link.
OPC Client and click
2. Enter a name for the OPC Server Link and click OK.
The OPC Server link is added to your project. Edit its properties in the Inspector.
Machine Edition OPC Servers
With Machine Edition OPC Servers, you can share your application’s data with
external OPC Client applications. This lets your Machine Edition application act
as a server in an OPC Client/Server relationship. The Machine Edition OPC
Servers support all required OPC interfaces in versions 1.0a and 2.0 of the OPC
specifications.
86
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
View Web Access
Machine Edition OPC Servers are automatically installed as part of View
Runtime and the Controller (sometimes referred to as the Logic Developer - PC
Controller). Downloading and running a project to a target automatically enables
the appropriate Machine Edition OPC Servers, based on the target’s
components. For example, if your project has a Logic component, Machine
Edition automatically enables the Logic Developer - PC OPC Server.
While configurating an OPC Client depends on the OPC Server, typically each
piece of data retrieved from a server is named an “OPC Item”. All OPC Clients
need to know how to address the data used by the server. The syntax for
retrieving OPC items from a Machine Edition OPC Server is as follows:.
Location Syntax
local
remote
<variable name>
<remote machine name>\ <variable name> or
<remote machine IP address>\ <variable name>
■
Local indicates that the appropriate Runtime is located on the same computer
as the Machine Edition OPC Server. Remote indicates that it is located on a
different computer.
■
The Machine Edition OPC Servers do not use access paths. Instead, as
described above, the path for remote access is included as part of each OPC
Item address.
VIEW WEB ACCESS
(Windows PC and QuickPanel View/Control targets only.)
Web Documents provide remote access to Machine Edition project data over an
Intranet or the Internet. When a Machine Edition project goes to run time, it
automatically launches an integrated web server. (You can configure this web
server with the ME Web Server applet in the Windows Control Panel.) Users
who connect to this web site are presented with the Site Index, which contains
different ways to view process information.
Navigator: Project tab
Web Document nodes
GFK-1868Q
■
Remote Views: Dynamic graphical recreations of actual panels from the
View Runtime display.
■
Custom Web Documents: Web pages generated using templates with
special HTML tags. These tags are periodically replaced with current project
data at run time. You can view web documents online or print them for
distribution.
Proficy* Machine Edition* 7.50 87
4
View*
View Web Access
■
Variable Monitor Browser: With this application, you can drag and drop
variables from Web Documents servers onto four unique viewing tools for
dynamic graphical representations of process data.
■
Remote Variable Inspector: With this tool, you can select a variable from a
list of project variables in a project and immediately receive the current value.
■
Web Control: With Web Control, you can write changes to a target’s data
from Web Documents. Before using this feature, ensure that your intranet
installation is secure and that no safety concerns exist with web control of a
target.
Want to know more? In the Help Index, look up “web” and choose “Web Access: an
Overview”.
To enabl e re mote acc ess t o your HMI pr oje ct
1. For each target that you want to allow remote access to, set the
target’s
Publish HMI property to True.
2. For each panel and variable in the target that you want users to be able to
access, set its Publish property to True.
For example, to allow users to view a graphical panel remotely, set the panel’s
Publish property to True.
To acce ss a publ i shed H MI ’ s S i te I ndex
1. Start Internet Explorer 5.5 SP4 or later.
2. In the Address box in Internet Explorer, enter the computer name or IP address
of the Runtime computer.
If you are not sure what the Runtime computer’s computer name or IP address
is, check the properties of the TCP/IP driver in the Control Panel Network setup
or contact your network administrator.
If you are testing the project on the local computer, enter “localhost” (without the
quotation marks) as the Address. This connects the browser to the local
computer.
88
■
When you connect to the run time computer, the Site Index appears with a list
of links to possible ways to view your process data.
■
The Site Index also includes a link to a page where you can download the
Web Documents Browser. With it, you can configure graphs, tables, and
ticker tapes to report on variables from several Machine Edition applications
simultaneously.
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
View Web Access
To view an HMI’s graphica l pa nels rem ote ly from a web browse r
You can also view graphical panels remotely from the Web Documents Site
Index.
1. Start Internet Explorer 4 or later.
2. In the Address box in Internet Explorer, enter the computer name or IP address
of the run time computer.
The Site Index appears.
3. Click Remote Views.
4. Click the panel you want to view.
After a few moments, the panel will load and run. Note that the panel must be
published for you to be able to view it remotely. To publish a panel, set its Publish
property to True.
Because the remote viewer uses a different graphics engine to draw and update
a graphical panel, there may be a few differences between the remote view of a
panel and its actual appearance on an HMI. For example, historical trend objects
on QuickPanel View/Control panels are not supported in remote views.
To add a new Cus tom We b D ocum ent
1. In the
Project tab of the Navigator, right-click the
and click New Web Document.
Web Documents node
2. Enter a name for your new document.
Your new
Custom Web Document appears beneath the Web Documents
node. You can edit properties of the Custom Web Document in the Inspector.
To edit a Cus tom W eb Docum ent
1. Outside Machine Edition, create an HTML, XML or text (txt.) document.
2. In the
Project tab of the Navigator, right-click the
you want to edit and click Web Document Files.
Custom Web Document
3. In the Web Document Files folder that appears, place your HTML document and
any logos or pictures your HTML document uses.
The Web Document is created from these files when you download your project.
You can view Custom Web Documents from the Site Index.
GFK-1868Q
Proficy* Machine Edition* 7.50 89
4
View*
Languages folder
LANGUAGES FOLDER
The
Languages item opens a grid that enables you to configure
multilanguage support for an HMI. At development time, you set up simple
translations between an original piece of text (named the “Source”) and one or
more languages. At run time, if the target’s Language Translation property is set
to Enabled, all text on the HMI’s graphical panels is translated based on one of
the language columns in the grid—the “Current Language”. That is, every
occurrence in the original text is replaced with its corresponding item in the
Current Language.
Navigator: Project tab
Languages node
During a validation or download, Machine Edition also checks the Source
column against all graphical panels to which you have made changes. Text
entries (in text objects and button objects) that do not appear in the Source
column are automatically added to the grid as rows with empty translations for all
languages.
The default language column used for translation is typically indicated with
yellow shading. You can also specify the Source language as the default
language, in which case the shading does not appear. How language translation
works depends on the target type:
Windows PC and QuickPanel View/Control targets: Machine Edition includes
the entire language table when downloading the project to the target. Translation
occurs dynamically at run time. The first language used for translation is the
default language. Within HMI scripts, you can change the current language used
for translation by calling the SetLanguage script function.
QuickPanel targets: Translation occurs only during the download operation,
based on the currently-specified default language. You cannot dynamically
change the current language at run time.
Want to know more? In the Help Index, look up “Languages folder”.
90
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
Languages folder
Working with the Languages editor
When you double-click a target’s
appears.
Languages node, the Languages grid
This column’s shaded yellow background
indicates that it is the default language. If
no column has yellow shading, then the
Source language is the default.
The “Source” column contains
the original words and phrases
to be used during the translation
process, as they appear in the
target’s graphical panels.
To enter a value into a
cell, double-click it (or
select the cell and start
typing).
If both the development and run time computers support
UniCode, you can use non-English character sets in the
grid (such as kanji, pictured). For example, In Windows
XP you can use the IME, configured in the Regional
Settings setup in the Control Panel.
The Languages Editor
To edit or enter the translation of a particular word for a language, double-click its
cell (or select the cell and either start typing or press F2). For a menu of
commands, right-click anything in the Languages grid.
To add a new language c olum n
1. Right-click in the Language Grid and click Insert Column.
A new, empty column is added to the grid.
2. Enter the name of the new language in the column’s header text box. To cancel
the addition of the column, leave the text box blank and click outside the column
header (or press ESC).
You can now edit the translation for the new language as normal.
GFK-1868Q
Proficy* Machine Edition* 7.50 91
4
View*
Languages folder
To renam e a language c olumn
• Right-click in the Languages Grid and click Rename Column (or double-click
the column header).
Enter the new name for the language in the column's header text box.
To move a la nguage column
1. In the Languages Grid click and hold the header of the column you want to
move.
2. Drag the mouse to the place where you want to move the column, then release
the mouse button.
To upda te e ntries in t he Sour ce colum n wit h ne w tex t ent ries in graphica l pa nels
• In the Navigator, under the target whose Languages grid you want to update,
right-click the Languages node and click Update Source Column.
View searches every graphical panel in the HMI (regardless of whether or not
the panel has changed since the last validation) and ensures that all text entries
can be found in the Languages grid.
To change t he display f ont for a la ngua ge
1. Right-click in the Languages grid, and click Set Column Font.
2. In the Font dialog box that appears, select the font you want to use to display the
entries in the Languages grid, along with the font style and other attributes.
The grid’s cells automatically resize to fit the height of the largest font used in the
grid.
3. Click OK when you are done.
The selected font set is used to display the translated text both in the Languages
grid and (in Windows PC and QuickPanel View/Control targets) the downloaded
HMI. Other font attributes—such as font sizes and styles—affect only how text
appears in the grid at development time.
To set t he def ault langua ge column
• In the Languages grid, right-click the column you want to set as the default
language and click Set Default Column.
The yellow highlight moves to the selected column. The next time you download
the project to the target with translations enabled, the default language will be
used by default. Note that you can also set the Source column as the default.
92
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
View Runtime
To de lete a la nguage colum n f rom t he grid:
• In the Languages grid, right-click the column you want to remove and click
Delete Column.
The column and all its translations are deleted.
This operation cannot be undone. Before deleting a language, ensure that you
no longer need information on translated words.
VIEW RUNTIME
(Windows PC and QuickPanel View/Control targets only.)
View Runtime is the program that runs your project’s completed HMI (human
machine interface) on a target computer. It uses the files downloaded to the
target during the download process. It is a separate application from Machine
Edition; while you can start View Runtime from within Machine Edition, you do
not need to be running Machine Edition to use it.
Want to know more? In the Help Index, look up “runtime” and choose “View Runtime: an
Overview”.
Networking
View Networking provides you with the flexibility to exchange data between run
time stations. Based on client-server relationships, and supporting a distributed
database system, View Networking allows access to any variable or alarm group
running on any other target on the computer network.
Want to know more? In the Help Index, look up “networking” and choose “View Networking:
an Overview”.
To run a project f rom Mac hine Edit ion
• In the
Project tab of the Navigator, right-click a target and click Download
and Start.
All components on the selected target are validated, downloaded to the specified
computer, and View Runtime is started. Errors listed in the Build tab of the
Feedback Zone must be corrected before a download can be completed. HMI
components are downloaded to View Runtime while logic components are
downloaded to the Controller.
GFK-1868Q
Proficy* Machine Edition* 7.50 93
4
View*
View Runtime
To run a n HMI proje ct out side Machine Edition
• On the Start menu, point to Programs, Proficy, and Proficy Machine Edition,
and click
View Runtime.
Runtime starts with the last project that was downloaded to that computer. View
Runtime opens with all graphical panels configured to appear at startup (that is,
all graphical panels whose Visible at Startup property is set to True).
To int era ct wit h View Runt ime
You can configure graphical objects so that you can change variable values,
trigger graphical animations, and execute custom scripts with a simple touch or
click.
You can monitor variable values, scripts, drivers, and the integrated web server
in Runtime through interfaces that can be opened using the following shortcut
keys:
94
To ...
Press ...
log in
log out
close Runtime
inspect and change variable values
view and debug scripts
view driver diagnostic information
open a panel
monitor the Web Documents server
display version information
CTRL+L
CTRL+U
CTRL+Z
CTRL+I
CTRL+G
CTRL+D
CTRL+O
CTRL+W
CTRL+B
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
QuickPanel Applications
QUICKPANEL APPLICATIONS
QuickPanel applications are HMI (human-machine interface) applications for
QuickPanel units. View supports development of HMI applications using
standard View and Machine Edition tools.
Development of an HMI for QuickPanel units is nearly identical to that of
Windows PC and QuickPanel View/Control units. Some of the differences are as
follows:
■
Navigator: Project tab
QuickPanel nodes
■
■
■
■
Graphical Objects: QuickPanel units support a slightly different set of
graphical objects than Windows PC and QuickPanel View/Control targets.
Also, QuickPanel units do not support Animation beyond that inherent in each
type of graphical object.
QuickPanel Panel Editor: The Panel Editor for QuickPanel applications
includes a tiling grid. This lets you easily align graphical objects with the
touch-sensitive cells on the QuickPanel unit’s screen.
Alarms: QuickPanel units support only Bit and Word Alarms.
Scripts: Scripts in QuickPanel applications use the proprietary QPScript
language. QuickPanel applications do not support ViewScript or VBScript.
For more information, see page 96.
Integration with Logic Developer - PLC: If you have Logic Developer - PLC
installed, you can use variables defined on a GE IP Controller target directly
in your QuickPanel application. To use this feature, both the GE IP Controller
target and the QuickPanel target must be part of the same project. You must
also configure an appropriate PLC Access driver and device on the
QuickPanel target, setting its PLC Target property to point to the GE IP
Controller target. (For more information about using GE IP Controller
variables, see GFK-1918: Getting Started Logic Developer - PLC.)
Want to know more? In the Help Index, look up “QuickPanel” and choose “QuickPanel
Applications: an Overview”, “QuickPanel Target”, and “QuickPanel vs.
Windows PC and QuickPanel View/Control application development”.
External Keypad Assignment
Some QuickPanel units support an external keypad. You enable the keypad by
setting the target’s External Keypad property to True; this enables keypad
configuration elsewhere in the application. There are two ways to assign an
action to a keystroke:
■
GFK-1868Q
In the graphical panel, graphical objects that can have an assigned keystroke
display a Key Assignment property. In this property, you can select a key that
will activate that graphical object just as if an operator tapped it on the display.
Proficy* Machine Edition* 7.50 95
4
View*
QuickPanel Applications
■
Actions not associated with a graphical object that appears in the panel are
configured in the Keypad Assignment grid. Each panel has a separate
Keypad Assignment grid.
To open the Keypad Assignment grid for a panel, select the panel’s Keypad
Assignment property and click its
button. Each row of the grid specifies the
action to perform when the user presses the indicated key while that panel (and
only that panel) is open.
Want to know more? In the Help Index look up “keypad” and choose “Keypad Assignment
Grid”. Also look up QuickPanel and choose “Working with QuickPanel
grid editors”.
Scripts on QuickPanel Targets
Scripts are sets of instructions that tell a project or panel how to react to events
during Runtime. Scripts on QuickPanel targets are written in a proprietary
language named “QPScript”. You create QuickPanel scripts with the same View
Script editor as Windows PC and QuickPanel View/Control targets (see page
75).
QuickPanel applications use two types of scripts:
Application Scripts: Application scripts are associated with a QuickPanel
target. These scripts can be executed any time your project is running on the
target platform. Application scripts are located under the
Application Scripts
folder in the Navigator.
Navigator: Project tab
QuickPanel Script Nodes
Panel Scripts: Panel scripts are associated with a graphical panel on a
QuickPanel target. All of a panel's scripts are located under its
Panel node in
the Navigator.
Want to know more? In the Help Index look up “QuickPanel” and choose “QuickPanel
Scripts: an Overview”.
QPScript Language
The QPScript language is composed of the following elements.
Statements: There are three general kinds of statements in a QPScript script:
■
Assignment statements set a variable’s value to the result of an expression.
■
Function calls execute one of the QPScript functions to perform a specific
operation.
■
Branching statements change the flow of script execution.
Keywords: The elements that make up these statements can be broken down
into the following categories:
96
Proficy* Machine Edition* 7.50
GFK-1868Q
View*
QuickPanel Applications
■
Operators are used in mathematical expressions and conditional
expressions.
■
Functions are predefined routines that perform various operations in the
QuickPanel application.
■
Keywords are other reserved words used in the QPScript language.
Expressions: There are two general kinds of expressions in QPScript:
■
Mathematical expressions produce numerical results.
■
Conditional expressions produce boolean results and are used in if-then-else
clauses.
Want to know more? In the Help Index, look up “QPScript” and choose “QPScript Language
Reference”.
GFK-1868Q
Proficy* Machine Edition* 7.50 97
4
98
View*
QuickPanel Applications
Proficy* Machine Edition* 7.50
GFK-1868Q
5
Motion Developer*
With Motion Developer, you can easily program GE’s S2K or Whedco’s IMC,
IMCjr (IMJ), and SMJ series of motion control devices. With Motion Developer,
you can:
■
■
■
■
Navigator: Project tab
Motion device nodes
■
Run easy-to-use wizards to set up and configure a complete motion control
system in a few mouse-clicks.
Add motion Controller targets to a Machine Edition project.
Edit motion blocks and programs for motion Controllers with the Motion
Developer Script editor.
Download programs and motion blocks to motion Controllers through a serial
port or a DeviceNet network.
Work online with a downloaded motion application, viewing and monitoring
variable values as the motion Controller’s programs run.
Motion Developer is fully integrated with the Machine Edition environment and
Machine Edition tools.
To crea te a Mot ion D evel ope r pr oje ct
1. In the
Manager tab of the Navigator, right-click
New.
The New Project dialog box appears.
My Computer and click
2. In the Project Name box, type a name for your project.
3. From the Project Template list, choose either the Motion Controller or Motion
Drive template and click OK.
When you select a template, a preview of what it includes is displayed.
4. Select the Series, Model, and Motor that corresponds with the Controller or drive
hardware and click OK.
Your new project is created and the Project tab is opened in the Navigator. If you
later need to change the Series, Model, or Motor, run the Target Configuration
Controller & Motor Setup wizard from the Main Wizard home page of the Motion
Developer target. (You can get to the Main Wizard by right-clicking the target and
selecting Main Wizard.)
GFK-1868Q
Proficy* Machine Edition* 7.50 99
5
Motion Developer*
About Motion Developer
ABOUT MOTION DEVELOPER
You use Motion Developer to develop motion applications on Windows-based
computers. Motion applications are loosely defined as a series of motion device
targets with programs, motion blocks, and configuration data. These applications
can then be downloaded to the motion Controller hardware, either directly
(through the computer’s serial port) or through a DeviceNet network.
In general, you go through the following phases when developing a motion
application:
1. Create a new Machine Edition project.
2. Add a Motion Controller or Motion Drive target to the project, depending
on the kind of motion device.
3. On each target, create the configuration script and (if appropriate) the
programs and motion blocks for the motion Controller or drive. The Motion
Wizards (see page 106) can make this easy.
4. Validate and download the application to the motion Controller.
The Motion Expert wizard takes you through these items step by step.
Supported motion control devices
Motion Developer supports the following lines of motion control devices.
GE IP motion control devices
Whedco motion control devices
S2K Controller/drive devices
S2K drive-only devices
IMC motion Controllers
IMCjr (IMJ) motion Controllers
SMJ drives
For more information, visit www.ge-ip.com.
Communication between the development computer and motion control devices
is supported over the COM port and over DeviceNet networks.
100
Proficy* Machine Edition* 7.50
GFK-1868Q
Motion Developer*
Motion Applications
MOTION APPLICATIONS
A typical Motion application consists of a single target. However, your project
can have as many targets as you want.
Motion targets
A
Motion target represents a run-time destination motion device that you
program and configure from Machine Edition. You need a separate target for
each physical motion device you configure, whether it is a Controller or a driveonly device.
When adding a Motion target, you specify either a Controller or a Drive target.
This determines the models of Controller you can select in its Controller Type
property.
■
Drive targets represent drive-only motion devices. This includes GE S2K
drive-only devices and Whedco SMJ devices. These targets have a
Configuration script only (page 102).
■
Controller targets represent Controller/drive motion devices. This includes
GE S2K Controller/drive devices and Whedco IMC and IMCjr (IMJ)
devices. These targets have a Configuration script (page 102), Motion
Programs (page 103), and can have several Motion Blocks (page 104). In
addition, they can make use of a CAM Profile (page 112).
To edit conf igur ation sc ripts, mot i on pr ogram s, and mot ion blocks
1. In the
Project tab of the Navigator, under the motion target, right-click
Configuration, or the
motion program or
motion block you want to edit
and click Open.
2. Create or edit the program in the appropriate editor.
3. After editing an item, download the program or project to the target hardware.
GFK-1868Q
Proficy* Machine Edition* 7.50
101
5
Motion Developer*
Motion Applications
To switc h be twee n a wizar d e ditor and t he mot ion sc ript edit or
Motion blocks and Motion programs can be edited either in a graphical wizard or
(for advanced users) in the motion script editor.
• In the
Project tab of the Navigator, under the motion Controller target’s
Programs folder, right-click the
motion program or
motion block whose
editing method you want to change.
■
If the item is set up to be edited in a wizard and you want to edit its script
directly, select Text View.
If the item is set up to be edited in scripts directly and you want to return to
using the wizards, select Flowchart View or Calculator View, as
appropriate.
When switching back to the graphical wizard, changes you made in the script
editor will be lost. The item will return to the state it was in when last edited in the
wizard.
■
Motion configuration
The motion Controller
configuration node represents a script used to
configure the motion Controller when the application is downloaded. This script
is used every time the entire application is downloaded to the motion Controller.
It can be downloaded any number of times. Typically, it sets default values for
registers and performs any necessary initialization commands.
■
Navigator: Project tab
Configuration node
■
You can create and edit a configuration script with the Motion Configuration
wizard (right-click
Configuration and click Wizard). This takes you through
motion Controller configuration step by step, creating a script based on
selected motor and axis parameters.
If you need more complexity, you can edit the script manually. You can do so
in the motion script editor (right-click
Configuration and click Open).
Want to know more? In the Help Index, look up “Motion Controller Configuration”.
Variable Dat a
The
Variable Data node contains commands that configure variable registers
for the target motion Controller. These include all VB, VF, VI, and VS registers.
Typically, these settings are acquired when you import a motion application from
a motion Controller unit and specify that variable values are included with the
import operation.
Only variables with data types and ranges specified during the import operation
are included. Later, when the application is downloaded to a motion target, these
102
Proficy* Machine Edition* 7.50
GFK-1868Q
Motion Developer*
Motion Applications
commands are executed on the connected motion Controller, duplicating the
imported variables.
Want to know more? In the Help Index, look up “Variable Data (Motion Controller)”.
CAM Dat a
The
CAM Data node contains commands that configure the CAM table for the
target. The CAM table defines a CAM profile, a curve that specifies the position
of a follower servo motor as a function of the master’s position.
Typically, these settings are acquired by including CAM points when validating a
target. You may also acquire CAM Data settings when you import a motion
application from a motion device that has CAM data. Either way, Motion
Developer automatically handles most CAM Data operations, so you should not
have to edit CAM Data settings at all.
CAM profiles are described in greater detail starting on page 112.
Want to know more? In the Help Index, look up “CAM Data (Motion Controller)”.
Motion programs
A
program represents one of the motion Controller’s programs. Programs are
scripts that control the operation of a motion Controller. With programs, you can
create complex behaviors for the Controller.
Motion Controller targets have four programs. These are added to the target
when you first create it. The last program ( Program 4) is the fault-handling
program, which determines the behavior of the Controller when an exception or
fault occurs. All programs for a target are located in its
Programs folder.
Want to know more? In the Help Index, look up “Fault-handling motion program”.
Navigator: Project tab
Motion Program nodes
You can edit programs either in the Application Builder (by default) or the Motion
Script Editor.
■
The Application Builder is a wizard that lets you visually specify the program
flow as a flowchart. For details, see page 108.
■
With the Motion Script editor, you can edit the script for a motion program
manually. For details, see page 105.
Want to know more? In the Help Index, look up “Motion Programs”.
GFK-1868Q
Proficy* Machine Edition* 7.50
103
5
Motion Developer*
Motion Applications
Motion blocks
A
Motion node represents a motion block for the motion Controller target.
Motion blocks are defined motions (that is, motion scripts) that can be called by
motion programs. With motion blocks, you can create complex motions—such
as blended moves—without the need for conditional or WAIT statements.
■
You can run motion blocks separately with the Controller Functions wizard
(see page 107).
You can create a motion block with the New Motion Block wizard (right-click the
Motions folder and click Wizard). This creates a complete motion block based on
your motion system.
Navigator: Project tab
■
Motion block nodes
Advanced users can create an empty motion block by right-clicking the
Motions folder and clicking Add.
After creating a motion block, you can edit it by right-clicking the motion block
and clicking Open. You edit motion blocks and motion programs either with the
Motion Calculator (see page 110) or in the Motion Developer Script editor (see
page 105).
Motion blocks have the following characteristics and restrictions:
■
Motion blocks complete executing one line of code before proceeding to the
next line of code.
■
Only one motion block per axis can run at the same time as the executing
program or programs.
■
When a motion block is executed, it overrides the currently executing motion
block.
■
You cannot use labels in a motion block.
Want to know more? In the Help Index, look up “Motion blocks”.
104
Proficy* Machine Edition* 7.50
GFK-1868Q
Motion Developer*
Motion Scripts
MOTION SCRIPTS
The Motion Script Editor interacts with other Machine Edition tools to provide the
most flexibility when editing a script. The following diagram illustrates some of
the operations you can perform.
Want to know more? In the Help Index, look up “editor” and choose “Working in the Motion
Script Editor”.
The Motion
Developer
drawer in the
Toolchest contains registers,
commands, and
operators you
can drag to a
motion script.
You can drag
variables from
the Variables
tab directly into
a motion script.
You can also
add items into
your script by
right-clicking in
the editor window.
The Companion
displays help for
the currently
selected register, command, or
operator.
There are several ways to insert items when writing motion scripts.
GFK-1868Q
■
If you are very familiar with the registers, commands, and operators used in
Motion scripts, start typing your script directly in the Script Editor.
■
If you need help with script keywords, you can add items with right-click
menus. Right-click where you want to insert an item and click Insert. Then,
point to what you want to include in your script and make a selection from the
list that appears. For a description of a register or command in the Script
editor, move the cursor on the word for which you need help and press F1.
■
The Motion drawer in the Toolchest contains items that you can drag into your
script. Leave the Companion window open for a description of each item.
■
You can also drag variables directly from the
into your script.
Variables tab of the Navigator
Proficy* Machine Edition* 7.50
105
5
Motion Developer*
Motion wizards
MOTION WIZARDS
Wizards are a series of screens that take you, step by step, through the creation
and configuration of your motion Controller application. In Motion Developer,
wizards appear in separate windows, so you can switch back and forth between
them.
The most commonly used Motion Developer wizards are as follows.
Main Wizard
Application Builder
Motion Calculator
Controller Functions
Provides access to several other wizards and tools for a motion
Controller target. Especially useful is the Motion Expert wizard,
which takes you through the creation of a complete application step
by step.
Enables you to create motion programs as a visual flowchart. See
page 108.
Enables you to define simple, incremental motions for motion
blocks. See page 110.
Provides access to several tools and online operations for the
motion Controller.
Navigat ing t hro ugh Mot ion wi zards
Pages of a Motion Developer wizard work just like HTML pages in a web
browser. Click buttons and hypertext links to move from page to page or to
perform the labeled task. Within a single wizard, you can move between steps
by clicking buttons in the top left corner of each page:
Click to close the wizard,
saving all changes you
made to the project.
Click to go to the previous page
Click to go to the next page
Click to close the wizard
without saving any changes
Buttons may be disabled depending on the situation. For example, if you are
using the AUTOTUNE page, the “Cancel” button is disabled.
Depending on the page, two additional buttons may be enabled in the top right
corner:
Click to jump to the first page in the wizard.
Click for more specific help on the current wizard or the current step.
106
Proficy* Machine Edition* 7.50
GFK-1868Q
Motion Developer*
Motion wizards
Many wizard pages contain tables of parameters. Edit the parameters based on
your system needs, then click Next. When editing parameters, you can also do
the following:
■
■
Click Use Last Saved Values to revert back to the last values saved for this
wizard page. Click Use Default Values to fill in parameters with default or
calculated values.
Click a parameter’s
button (to the right of its entry text box) for a short
description, including its minimum, maximum, and default values. Click the
button for a more detailed description of that parameter.
Wizards for different targets, motions, and programs open in separate windows.
You can switch between windows by clicking the tabs at the bottom of the editor
window display.
Two of the most important wizards are the Main Wizard and the Controller
Functions/Drive Functions wizard:
■
■
■
■
GFK-1868Q
The Main Wizard page provides access to most other major Motion
Developer wizards and tools. This includes the Motion Expert wizard, which
takes you through the creation of a complete Motion Developer project step
by step. To open the Main Wizard page for a target, right-click the
target
and select Main Wizard.
With the Controller Functions and Drive Functions wizards, you can perform
diagnostic and other operations on the motion Controller. Functions on these
wizards have no effect if the local computer is not connected to a motion
Controller. To access these wizards, double-click the target you want to
perform the functions on or, while working with a target, click the
Controller/Drive Functions button.
Want to know more?
For a description of the wizards available from the Main Wizard page, in the Help Index, look
up “Main Wizard page”.
For a description of features available from the Controller Functions wizard page, in the Help
Index, look up “Controller Functions wizard”.
Proficy* Machine Edition* 7.50
107
5
Motion Developer*
Special Wizards
SPECIAL WIZARDS
The Application Builder and the Motion Controller wizards deserve special
mention. They enable you to edit parts of your motion application in graphical
editors.
Application Builder flowchart editor
With the Application Builder, you can edit your motion programs as a simple
flowchart. This makes it easy to see exactly how your finished application will
run.
The flowchart editor looks something like this:
The Application Builder toolbar (see below).
Click these buttons to perform operations
on the program or selected step.
A Motion step. You can select from any of
the target’s Motion blocks. To add new
motion blocks to a target, click the Add
Homing Motion or Add Motion buttons.
The selected step. Click a step to select it.
The “True” branch from a conditional step
(see page 109). If MB is True, the program
skips the DO7=Off step.
Use the scroll bar to scroll up and down
through the flowchart.
The following two buttons on the toolbar open wizards that enable you to add
new motion blocks to the target.
■
Click Add Homing Motion to add one of many predefined homing motions.
■
Click Add Motion to add a predefined non-homing motion, or to use the
Motion Calculator (see page 110).
After adding the desired motion blocks, click Finish to return to the flowchart
editor.
Want to know more? In the Help Index, look up “Motion Application Builder”.
108
Proficy* Machine Edition* 7.50
GFK-1868Q
Motion Developer*
Special Wizards
Basic f lowchart step t ypes The flowchart is composed of the following basic step types.
■
Start and End steps: Flowchart execution begins at the Start step. When
execution reaches the End step, the program stops.
■
Logic steps: Performs a logic-oriented action, such as setting or resetting a
particular register.
■
Motion Program steps: Performs a motion program action, such as starting
or stopping a program.
■
Motion block steps: Runs a motion block.
■
Delay steps: Pauses program execution.
■
Conditional and Connector steps: Evaluates a given condition and
branches execution depending on the results. For more details, see
Conditional Steps on page 109 (or look up “Connecting and disconnecting
conditional steps” in the online help).
■
User-defined steps: Performs a piece of motion script entered by you.
■
Remark steps: Enables you to insert a comment into the flowchart. Remarks
are included in the script downloaded to the motion Controller.
■
Comment steps: Enables you to insert a comment into the flowchart.
Comments are not included in the script downloaded to the motion Controller.
Conditional steps are described in greater detail below.
Want to know more? In the Help Index, look up “Application Builder step types”.
Conditi onal steps
Conditional steps represent a simple conditional statement. When program
execution reaches a conditional step, it branches depending on a specified
expression:
Steps here are executed only if FI =
0 (that is, if the expression is false).
■
If the expression is True, execution branches to the right (indicated by a “T”).
■
If the expression in the statement is False, execution branches downward.
You can choose from several conditional expressions, including several that
refer to fault registers. Selecting a conditional step or connector highlights the
line connecting it to its partner.
GFK-1868Q
Proficy* Machine Edition* 7.50
109
5
Motion Developer*
Special Wizards
T o ins ert a n ew st ep int o the A p p li ca ti o n Bui l d er f lo wc hart
1. In the Application Builder flowchart, select the step immediately preceding the
spot where the new step will go.
To add a step to the beginning of the flowchart, select the Start step.
2. Click the
Add Command button on the Application Builder toolbar.
In the menu that appears, point to the type of command or step you want to add,
then select the exact step from the submenu. Connector steps, Comments, and
User-defined steps are found under the Standard Elements option.
Some command types may be unavailable depending on your project. For
example, you cannot add a Motion step until the target has some motion blocks.
3. The new step appears after the originally selected step.
If necessary, you can move the step to a different position, or (if appropriate) edit
the step’s parameters.
To edit a st ep in the Applica tion Builder fl owc hart
• In the Application Builder, do one of the following:
■
Double-click the step.
- or -
■
Right-click the step and choose Edit (if the step is editable).
- or -
■
Select the step, then click
toolbar.
Edit Command on the Application Builder
- or Select the step, then press CTRL+E.
Only certain steps have parameters that can be edited. If a selected step cannot
be edited, the Edit Command button is disabled.
■
Motion Calculator
The Motion Calculator is the default editor for motion blocks. With it, you can
create simple incremental motion blocks based on mathematical calculations,
viewing the results of changes as you make them.
You can open the Add Motion wizard by right-clicking the Motions folder in the
Navigator and clicking Wizard. Unless you configure a motion block to be edited
as text, the Motion Calculator also opens when you right-click a motion block
and click Open.
110
Proficy* Machine Edition* 7.50
GFK-1868Q
Motion Developer*
Special Wizards
The Motion Calculator looks something like this:
Click one of these to select the kind of motion you want.
Click these buttons to zoom in and out of
the graph of the plotted motion.
Click the arrows to pan around the graph of
the plotted motion.
Click here to print the graph of the plotted
motion on the default printer.
You can enter values for two of these three
parameters. (The third is calculated.)
Enter new values for Acceleration time and
Deceleration Time to override the defaults.
Click here to clear all values for the current
motion.
Calculated values appear in the Calc column.
Enter your own values in the Data column.
Click here to fill in the Calc column and view (or update) a velocity/time graph of the
calculated motion.
Typically, you would enter desired values in the Data column and click
Calculate. The Motion Calculator updates the appropriate values in the Calc
column and draws a velocity/time graph of the calculated motion. Units in this
graph are based on those in the Units column.
When entering values into the calculator, keep in mind the following:
■
You can fill in two (and only two) of Velocity, Total Time, and Distance. That is,
one of these parameters must be left at 0 and the other two filled in with nonzero values. The Motion Calculator automatically calculates the missing
parameter in the Calc column.
■
If you leave Acceleration time (Acc. Time) or Deceleration time (Dec. Time)
as 0, they are set to one-third the total time for the motion. You can override
this by filling in the appropriate parameter.
When the motion is configured the way you want, click Add Motion (above the
calculator in the wizard page) to add the motion block to your application.
GFK-1868Q
Proficy* Machine Edition* 7.50
111
5
Motion Developer*
CAM Profile Editor
CAM PROFILE EDITOR
The Motion Developer CAM editor lets you create and edit electronic CAM
profiles for a motion Controller target. A CAM profile is a curve that specifies the
response of a slave servo to a master position index. The CAM profile is written
to the target’s configuration script. You can create as many profiles as you want,
but only one can be downloaded to a target at a time. The profile that is
downloaded is specified in the target’s “CAM Profile” property.
You can edit a target’s CAM Profiles by double-clicking its
Profile node under
the
CAM Profiles folder. The CAM editor display appears as follows:
Navigator: Project tab
CAM Profile nodes
Double-click a CAM
Profile node in the
Navigator to open the
CAM editor.
Curves of the
profile can be
adjusted and
edited graphically
The CAM profile table
supports numeric editing and curve order
grouping
Secondary
curves show the
velocity, acceleration, and jerk
of the CAM profile.
The Companion automatically provides
information on what
you click.
You can adjust the curves of your CAM profile to suit the specific needs of your
project. With the CAM editor you create profiles by defining points on a
master/slave position curve. Groups of adjoining points are allocated to sectors.
Each sector is assigned a polynomial curve fit order (1,2,3) that specifies how
the curve will be interpolated between points.
To include CAM Profile data when downloading your project, ensure that the
target’s Include CAM Points property is set to True. When downloading a project
to a target with a defined CAM Profile, Motion Developer automatically converts
the curve to a series of CAMx=value commands. These commands are added to
the target’s
CAM Data node.
112
Proficy* Machine Edition* 7.50
GFK-1868Q
Motion Developer*
CAM Profile Editor
The number of CAMx commands added to the configuration script depends on
the target’s CAM Point Resolution property.
■
If CAM point Resolution is 1 degree, 360 CAM commands are added to the
script.
■
If CAM point Resolution is 0.1 degrees, 3600 CAM commands are added to
the script.
Downloading 3600 CAM commands can be very time-consuming. It is therefore
recommended that you use a Resolution of 1 degree, at least during the initial
development stages.
Want to know more? In the Help Index, look up “Motion Developer CAM Editor: an
Overview”.
To add a new CA M Profile t o a mot ion Cont roller t arget
1. In the
Project tab of the Navigator, right-click the
motion Controller target’s
CAM Profiles folder and click New Profile.
A new Profile appears under the CAM Profiles folder.
2. Enter a new name for the Profile.
You can now open the profile in the CAM Editor. Note that only one CAM profile
can be downloaded to a motion Controller at a time.
To edit a CA M prof ile on a moti on Cont roller ta rget
• In the
Project tab of the Navigator, under the
motion Controller target’s
CAM Profiles folder, right-click the
Profile you want to edit and click
Open Profile (or just double-click the Profile).
The CAM editor opens with the target’s CAM profile.
For more details on using the profile editor, look up “Editing a Motion CAM
Profile” in the online help.
To specif y the C AM Pr ofile tha t get s downloaded to t he mot ion C ontroller t arget
1. In the
Project tab of the Navigator, right-click the
motion Controller target
for which you want to select a CAM Profile and click Properties.
The
Inspector displays the CAM profile’s properties.
2. If necessary, in the Inspector, set the target’s Include CAM point property to
True.
This ensures that Machine Edition includes CAM profile data the next time you
download the application to the motion Controller.
3. In the Inspector, select the desired CAM Profile in the target’s CAM Profile
property.
GFK-1868Q
Proficy* Machine Edition* 7.50
113
This property appears only if Include CAM point is set to True. You can select
from all CAM Profiles configured for the target.
Index
A
Build tab 26
actions 45, 46
Active scripting 77
adding
alarm groups (Bit and Word) 81
CAM Profiles 113
Control I/O drivers 63
custom web documents 89
language columns 91
logging groups 83
logic component 40
Machine Edition projects 20
OPC server links 86
panels 72
PLC Access drivers 84
alarm groups 80
alarms 80
Alarm Display objects 81
alarm groups 80
Bit Alarms 80
setting alarm conditions 81
Variable Alarms 80
Word Alarms 80
Allen-Bradley RIO 62
animation
graphical objects 74
touch animation scripts 75
Application Builder
about 108
conditional steps 109
inserting steps 110
See alsosteps, flowchart
application scripts 75, 79, 96
applications, motion 101
ASCII drivers 62
authorization. See product authorization
C
B
backing up projects 20
Bit Alarms 80
blocks, motion. See motion blocks
blue arrows. See docking markers
branches 46
GFK-1868Q
Calculator, Motion See Motion Calculator
CAM data 103, 112
CAM point resolution 113
CAM Profiles
specifying for download 113
CAM profiles
about 112
adding 113
editing 113
editor 112
client
networking 93
OPC 86
Companion 18, 46, 50, 53, 56
component
logic 40
conditional steps 109
configuration
CAM data 103
motion script 102
variable data 102
configuring
alarm conditions 80
Control I/O 64
Controller 66
panels 73
PLC Access I/O 83
properties 22
user preferences 21
Control I/O 63
tool 63
working with 64
Controller 65
configuring 66
going online 31
going online (IL) 51
going online (ST) 54
running 67
scan cycle 65
Controller Functions wizard 107
Proficy* Machine Edition* 7.50
115
controller/drive targets, motion 101
correcting, errors 35
creating
actions 46
alarm display objects 82
alarm groups (Variable) 81
application scripts 75
FBDs 55
IL blocks 49
macros 42
panel scripts 76
projects 20, 32, 71
SFCs 42
ST blocks 52
subroutines 46
touch animation scripts 76
variables 33
custom web documents 89
adding 89
editing 89
D
Data Watch 47
debugging scripts 94
developing. See creating
DeviceNet 62
devices
adding to PLC Access driver 84, 85
motion control 100
PLC Access 83, 84
docking markers 19
downloading 31, 35, 66
QuickPanel View/Control 36
motion device targets 35
QuickPanel View/Control targets 36
specifying CAM profile for 113
Windows PC targets 35
drawing graphical objects 73
drawing tools 73
Drive Functions wizard 107
drive targets, motion 101
drivers
adding
Control I/O 63
PLC Access I/O 84
ASCII 62
Control I/O 62, 63
116
Proficy* Machine Edition* 7.50
Control Peer 62
OPC Client 86
PLC Access I/O 83
E
editing
application scripts 75
CAM profiles 113
custom web documents 89
FBDs
offline 56
online 58
IL blocks
offline 50, 51
ladder programs
offline 46
online 47
motion scripts 105
panel scripts 76
panels 73
quick editing
ladder program 47
SFCs 43
quick test 37
SFCs
offline 42
online 44
steps, flowchart 110
structured text
offline 53
online 54
editors
function block diagram (FBD) 55
grid (QuickPanel) 79
instruction list (IL) 49, 52
ladder 45
panel 72
script 75, 96
structured text (ST) 52
errors and warnings
correcting 35
Feedback Zone 26
external keypad 95
F
FBD Editor
online 58
FBD editor
GFK-1868Q
offline 56
FBD instructions 56
inserting from the FBD editor 57
inserting from the Toolchest 57
FBD text boxes
inserting from the FBD editor 57
inserting from the Toolchest 56
FBDs
creating 55
editing 56, 58
opening 55
Feedback Zone 26
fixing, project errors 35
flowchart editor See Application Builder
flowchart steps See steps, flowchart
full-text search 17
Function Block Diagram (FBD) editor 55
G
GE Genius 62
getting help 17
global function library scripts 75
graphical objects 72
animating 74
drawing 73
graphical panels. See Panels
grid editor
keypad assignment 95
messages 74
H
editing 50, 51
opening 49
IL Editor
offline 50
IL editor
offline 51
Import tab 26
index, search 17
Indexed Image Display (IID) 74
Indexed Message Display (IMD) 74
InfoView tab 20
InfoViewer 18
inserting
FBD instructions 56
FBD instructions (FBD editor)) 57
FBD instructions (Toolchest) 57
FBD text boxes (FBD editor) 57
FBD text boxes (Toolchest) 56
IL instructions 50
ladder instructions 46
motion script items 105
rungs 46
script functions 78
SFC instructions 43
ST instructions 53
Inspector 22
Inspector. See Inspector
installing Machine Edition 4
Instruction List (IL) Editor 49
Instruction List (IL) editor 52
Internationalization. See Languages folder
hardware
motion devices 100
Hardware Key Authorization 5
help 17
Historian Collector 82
K
I
labels 45
Ladder Editor 45
offline 46
online 47
ladder instructions 46
ladder programs
defined 45
editing
offline 46
online 47
opening 45
I/O
configuring
Control 64
PLC Access 84
Control 63
OPC 85
IEC addresses 64
IL blocks
creating 49
GFK-1868Q
keypad assignment 95
keyword search 17
L
Proficy* Machine Edition* 7.50
117
quick editing 47
Language translation 90
Languages folder 90
adding new languages 91
grid 91
moving language columns 92
renaming languages 92
Languages grid 91
default language 92
delete language 93
display font 92
updating Source language 92
locating
labels 45
variables 42, 46, 50, 53, 56
logging data 82
enabling logging for a variable 82
logging groups 82
adding 83
logging strategies 82
Logic Developer
PC 39 to ??
Logic Developer - PC 39 to ??
logic, adding 40
M
Machine Edition
downloading 35
environment 16
getting help 17
key features 17 to 27
OPC servers 86
projects 20, 29
properties 22
toolbars 19
validating 35
macros 42
Main Motion Wizard 107
Manager tab 20
message grids 74
messages 74
Indexed Image Display (IID) 74
Indexed Message Display (IMD) 74
Triggered Message Display (TMD) 74
Messages tab 26
Modicon Quantum 800 62
Motion applications
configuration script 102
118
Proficy* Machine Edition* 7.50
programs 103
motion applications 101
motion blocks
about 104
editing with calculator 110
opening 101
switching editors 102
Motion Calculator
about 110
using 111
motion configuration 102
opening 101
Motion Developer
applications 101
supported hardware 100
Motion programs
fault-handing program 103
opening 101
switching editors 102
motion programs 103
motion scripts 105
motion targets 101
Motion Wizards
about 106
Application Builder 108
Controller Functions 107
Drive Functions 107
Main Wizard 107
navigating through 106
parameters 107
See also Motion Calculator
special wizards 108
moving product authorization 8
multi-language support. See Languages folder
N
Navigator 20
property column view. See Property column view
networking 93
O
objects. See graphical objects
offline
FBD editor 56
IL Editor 50
IL editor 51
Ladder Editor 46
SFC Editor 42
GFK-1868Q
ST editor 53
online
FBD Editor 58
Ladder Editor 47
SFC Editor 44
ST editor 54
to the Controller 31
to the Controller (IL) 51
to the Controller (ST) 54
online help 17
OPC 85
client 86
server links 86
servers 86
opening
application scripts 75
FBDs 55
IL blocks 49
ladder programs 45
macros 42
motion blocks, motion programs, and motion
configuration 101
panel scripts 76
panels 72
projects 21, 30, 32, 40, 71, 99
SFCs 42
ST blocks 52
Options tab 21
options, user preferences 21
P
Panel editor 72
animation 74
graphical objects 72
working with 73
panel scripts 75, 79, 96
panels 72
adding 72
configuring 73
editing 73
opening 72
quick testing 37
parameters, Motion Wizards 107
peer driver, Control 62
phrase search 17
PLC Access I/O 83
preview panels. See quick test
Product Authorization 5
GFK-1868Q
product authorization
authorizing Machine Edition 7
moving to another PC 8
Proficy Historian 2.0 82
profiles, CAM See steps, flowchart
programs, motion See motion programs
Project tab 21
Projects
Shared 29
projects 20, 29
adding 20
backing up 20
creating 20, 32
downloading 35
Motion Developer 99
opening 21, 30, 32, 40, 71, 99
running 30, 93
sharing between Machine Edition workstations 29
validating 35
with HMI component 71
with logic component 40
properties 22
configuring 27
Property column view 27
proxy variables 84
Q
QPScript language 96
quick editing
ladder program 47
SFCs 43
quick start 14
quick test, panels 37
QuickPanel
scripts 96
QuickPanel Applications 95
QuickPanel Grid editor 79
QuickPanel View/Control
downloading 36
QuickPanel View/Control targets 32
downloading 36
R
References tab 26
remote views 89
Reports
variable 28
Reports tab 26
Proficy* Machine Edition* 7.50
119
requirements, hardware and software 2
resolution, CAM point 113
rungs 45
inserting 46
write changes 48
running
Controller 67
projects 30, 93
sample applications 30
View Runtime 93
S
sample applications 30
scan cycle, Controller 65
script commands. See script functions
Script editor 75, 96
inserting script functions 78
scripts 75, 96
working with 78
script functions 78
scripting languages
Active scripting 77
QPScript 96
VBScript 76
ViewScript 76
scripts 75, 96
application scripts 75, 96
debugging 94
global function library scripts 75
inserting script functions 78
motion 105
panel scripts 75, 96
touch animation scripts 75
scripts, motion
inserting items 105
search, full-text 17
search, index 17
Sequential Function Charts. See SFCs
servers
networking 93
OPC 86
setting. See configuring
SFC Editor
offline 42
online 44
SFC instructions, inserting 43
SFCs
editing 42
opening 42
quick editing 43
Shared Projects 29
shortcut keys, View Runtime 94
shunts 46
Site Index 88
Smart Lists 24
Software Key 6
ST blocks
creating 52
opening 52
ST editor
offline 53
online 54
ST instructions
inserting 53
steps, flowchart
conditional 109
editing 110
inserting 110
step types 109
structured text
editing 53, 54
Structured Text (ST) editor 52
subroutines 46
switching editors, motion blocks and motion programs 102
system requirements 2
T
tags. See variables
targets 29, 32
motion 101
testing
panels 37
scripts 94
toolbars
drawing tools 73
ladder instruction tools 46
Machine Edition tools 19
Toolchest 25, 46, 56
tools
Companion 18
Control I/O 63
Data Watch 47
docking markers 19
Feedback Zone 26
InfoViewer 18
Inspector 22
Navigator 20
overview 16
toolbars 19
Toolchest 25, 46, 56
touch animation scripts 75
translations. See Languages folder
Triggered Message Display (TMD) 74
testing the HMI 37
View Runtime 93
running 94
shortcut keys 94
ViewScript language 76, 77
U
W
Unused Variable report 28
user preferences 21
Warm Standby 67
and OPC servers 69
configuring 68, 69
configuring OPC server for 69
warnings 35
Feedback Zone 26
watching variable values 58
Web Access 87
Site Index 88
Windows PC targets 29, 32
downloading 35
windows. See Panels
wizard, Controller Functions 107
wizard, Drive Functions 107
Wizard, Main 107
wizards, motion See Motion Wizards
Word Alarms 80
word search 17
writing motion scripts 105
writing scripts 78
V
validating 26, 35, 66
Variable
property column view 27
Variable Alarms 80
variable data 102
Variables 27
managing 27
reports 28
variables
creating 33
locating 42, 46, 50, 53, 56
proxy 84
watching values 58
Variables tab 21, 27
VBScript language 77
View 71 to 97
GFK-1868Q
Proficy* Machine Edition* 7.50
121
122
Proficy* Machine Edition* 7.50
GFK-1868Q
Скачать